background image

6

SunTouch TapeMat Installation Manual

Tips

Co ntrols:

 The SunStat controls will provide direct 

floor-warming control or can be set to sense air 

temperature with a floor temperature limit. Other controls 

may not give the same desired level of control or overall 

comfort and are not recommended.

Lo udMouth™:

 The LoudMouth is a continuity monitor with an 

integrated alarm. An alarm will sound if damage occurs to 

the heating wire during installation. The LoudMouth stays 

connected to the power leads throughout the TapeMat 

installation. A small screwdriver for connecting the leads is 

included with the LoudMouth monitor.

INSPECT CABLE, CONTROL, and SENSOR

STEP 2.1

   Remove the TapeMat, control, and sensor from their 

packages. Inspect them for any visible damage  

and verify everything is the correct size and type  

according to the plan and the order. Do not attempt to  

install a damaged product.

STEP 2.2

   Record the product information in 

Table 4

. Give this 

information to the homeowner to keep in a safe place.

   The TapeMat model number, serial number, voltage, and 

resistance range are shown on a nameplate label attached 

to the power leads, as well as the marking "(x)-FOR INDOOR 

FLOOR HEATING APPLICATIONS".  

Do not remove this nameplate label. The electrical 

inspector will need to see this.

STEP 2.3

   Use a digital multi-meter set to the 200Ω or 2000Ω (2kΩ) 

range to measure the resistance between the conductors 

of the mat power leads. Record these resistances in 

Table 4

 

under “Out of the box before installation”.

   The resistance should measure within the resistance range 

on the nameplate label. If it is a little low, it may be due 

to low air temperatures or meter calibration. Consult the 

factory if in doubt. 

 

   

CAUTION:

 Make sure power is not applied to the 

product until it is fully installed and ready for final 

testing. All work must be done with power turned  

off to the circuit being worked on. 

Record the information from the  

nameplate label into the Mat 

and Sensor Resistance Log. 

Leave the nameplate label 

attached to the power leads for 

later inspection.

Press the test lead tips to the Black and White (or Blue for 240 VAC) power lead wires. 

This reading should correspond to the factory resistance range on the nameplate label 

attached to the Power lead.
Readings between the White (or Blue for 240 VAC) and Ground or the Black and Ground 

power lead wires should measure “open”, or “O.L”, or the same as displayed when the test 

leads are not touching anything.

Black Lead

White or Blue Lead

Ground Lead

Black Lead

200 ohm setting

Black wire to COM

Red wire to 

Ω

White or Blue Lead

Ground Lead

Black Lead

White or Blue Lead

Ground Lead

Summary of Contents for TapeMat D12

Page 1: ...ation Manual TapeMat Series D12 Please be aware local codes may require this product and or the thermostatic control to be installed or connected by an electrician Please leave this manual with the en...

Page 2: ...tails Minimum bend radius 1 inch Maximum exposure temperature Continuous and storage 194 F 90 C Minimum installation temperature 50 F 10 C Skill Level Installation must be performed by qualified perso...

Page 3: ...der cabinets or other built ins having no floor clearance or in small closets Excessive heat will build up in these confined spaces and the mat can be damaged by fasteners nails screws etc used to ins...

Page 4: ...pedestals support columns walls or similar Install the heating wires 4 to 6 away from the perimeter walls of the room It may be placed closer but is unnecessary since most people do not stand this cl...

Page 5: ...7024 7 0 24 29 160 2 x 80 24008024 8 0 22 27 3 ft Wide 30 3 x 10 24001036 1 5 144 176 40 3 x 13 4 24001336 2 0 97 118 50 3 x 16 8 24001636 2 5 78 95 60 3 x 20 24002036 3 0 60 74 90 3 x 30 24003036 4 5...

Page 6: ...R FLOOR HEATING APPLICATIONS Do not remove this nameplate label The electrical inspector will need to see this STEP 2 3 Use a digital multi meter set to the 200 or 2000 2k range to measure the resista...

Page 7: ...temperature sensed Table 3 provides approximate resistance to temperature values for reference The LoudMouth monitor sold separately will constantly monitor theheatingwireduringtheentireinstallationp...

Page 8: ...ch have lighting motors exhaust fans or hot tub pumps due to possible interference STEP 3 2 Install Electrical Boxes SunStat Thermostat Install an extra deep electrical box for the SunStat thermostat...

Page 9: ...power leads to avoid possible interference Open a separate knock out in the bottom of the thermostat box Feed the sensor and conduit if used through the knock out down through the cut out in the botto...

Page 10: ...ke sure the power lead factory splice is to be completely flat and in the floor mortar not in the wall STEP 4 4 Test Fit the Mat Roll out the mat flipping it as needed to cover the intended area This...

Page 11: ...age can result DO NOT use nails duct tape other types of tape or other unapproved fasteners to hold the heating wire or mesh in place Damage can result STEP 4 6 Use a digital multi meter to measure th...

Page 12: ...r Tape Conduit Power Lead Factory Splice in thin set not in conduit STEP 4 10 Shower Application Note Acceptance of this application must be verified by the local inspector or authority having jurisdi...

Page 13: ...when installing a radiant product Do not use solvent based adhesives or pre mix mortars because they are not as heat resistant Select the proper size trowel for the installation of tile or stone We re...

Page 14: ...strengthen the floor Tapemat can be installed in either the mor tar bed dry set or in the mortar bond coat directly below the tile or stone TapeMat is generally installed above the self leveling morta...

Page 15: ...tion until the tile or flooring installer verifies all cement materials are fully cured typically two to four weeks See mortar manufacturer s instructions for recommended curing time NOTE Most laminat...

Page 16: ...16 SunTouch TapeMat Installation Manual Appendix 90 orFlipTurn Roll overTurn 180 orBack to BackTurn Fill inTechnique Typesofturns Step by steplayoutforatypicalbathroom 1 2 3 4 5 6 7 8...

Page 17: ...area The controlsshouldNEVERbeinstalledintheshower area orwhereanyoneintheshowercouldtouch thecontrols Installthecontrolsaminimumof4 awayfromtheshowerarea Neverinstallthemat inshowerwalls or anyotherw...

Page 18: ...ink Smallbathlayout2 One3 x8 4 mat Doorway Doorway BathTub Vanity Smallbathlayout1 One3 x5 mat Frontentrywaylayout Two3 x10 mats one3 x5 mat Control Installmatsrightuptothe faceofthevanity Theheat tra...

Page 19: ...electrician in accordance with local building and electri cal codes and the National Electrical Code NEC espe cially Article 424 of the NEC ANSI NFPA70 and Section 62 of CEC Part 1 CAUTION Make sure 1...

Page 20: ...rol and Relays Use size 18 to 24 gauge 2 conductor wire up to 100 feet 30 m in length to connect SunStat to SunStat Relay Typical Wiring for SunStat with SunStat Relay s 20 amp circuit for each SunSta...

Page 21: ...all codes for wiring If in doubt consult an electrician Illustration showing how to connect three mats at the thermostatic control electrical box Illustrationshowinghowtoconnectmultiple matsfrommultip...

Page 22: ...ufacturer If mat is not damaged replace the GFCI control Also see GFCI conflicts below Incorrect voltage supplied or mismatched electrical components used Measure line voltage then measure load voltag...

Page 23: ...THER DISCLAIMS ANY RESPONSIBILITY FOR SPECIAL INDIRECT SECONDARY INCIDENTAL OR CONSEQUENTIAL DAMAGES ARISING FROM OWNERSHIP OR USE OF THIS PRODUCT INCLUDING INCONVENIENCE OR LOSS OF USE THERE ARE NO W...

Page 24: ...eld MO 65803 Ph 888 432 8932 Fax 417 831 4067 Web suntouch com SunTouch aWattsRadiantproduct WattsRadiant aWattsWaterTechnologiesCompany Affiliations The SunTouch manufacturing facility s Quality Syst...

Reviews: