![SunSynk SUNSYNK-8K-SG01LP1 Installer Manual Download Page 62](http://html1.mh-extra.com/html/sunsynk/sunsynk-8k-sg01lp1/sunsynk-8k-sg01lp1_installer-manual_1400632062.webp)
Page | 62
Hybrid Inverter | Installer Manual
5.17. Advanced Settings for Paralleling Inverters
To configure multi-inverter settings, click on the ADVANCE icon.
What this page displays:
If the inverter operates as a master or a slave.
Modbus Device ID – ‘Modbus SN’ that must be unique for each inverter connected to the
bus/wire.
What you can do from this page:
Set the inverter as a master or slave per bus/wire.
Set the phase in which the inverter will be paralleled.
Set the Modbus SN for paralleling.
The Sunsynk parity inverter can be wired standalone or where more power is required it can be
connected in parallel either single or 3 phase configuration. The maximum number of inverters
that can be paralleled in a single phase utility grid is three and the maximum number that can
be paralleled in a three phase utility grid is fifteen.
To parallel six inverters in a three phase utility grid is necessary to set three inverters as master
and three as slaves:
Phase A: Master A and Slave A
Phase B: Master B and Slave B
Phase C: Master C and Slave C
Summary of Contents for SUNSYNK-8K-SG01LP1
Page 9: ...2 1 Product Size Page 9 Hybrid Inverter Installer Manual Inverter Size...
Page 16: ...Page 16 Hybrid Inverter Installer Manual 4 5 Function Port Definition...
Page 20: ...Page 20 Hybrid Inverter Installer Manual...
Page 22: ...Page 22 Hybrid Inverter Installer Manual 4 9 1 Recommended AC Surge Protector...
Page 28: ...Page 28 Hybrid Inverter Installer Manual 4 13 Wiring System for Inverter...
Page 29: ...Page 29 Hybrid Inverter Installer Manual...
Page 34: ...03 02 01 Page 34 Hybrid Inverter Installer Manual...
Page 37: ...Page 37 Hybrid Inverter Installer Manual 4 19 2 Connected to a Generator 03 02 01...