4.9. Connecting the AC
Please follow the steps below to implement GRID, LOAD, and GEN port connections:
1. Before making GRID, LOAD, and GEN port connections, make sure to turn off the AC
breaker or disconnector first.
2. Remove 10mm sleeve from each wire, unscrew the bolts, insert the wires according to the
polarities indicated on the terminal block and tighten the terminal screws. Ensure the con-
nection is complete.
3. Then, insert AC output wires according to polarities indicated on the terminal block and
tighten the terminal. Make sure to connect corresponding N wires and PE wires to related
terminals as well.
4. Ensure the wires are securely connected.
5. Check that the AC power source is isolated before attempting to connect it to the inverter.
Insert AC output wires according to the polarities indicated on the terminal block and tighten
the terminal screws. Be sure to connect corresponding N wires and PE wires to the correct
terminals and ensure the wires are securely connected.
Model
Wire Size
Cable(mm
2
)
Torque value (max.)
8kW
10AWG
8
1.2N.m
All wiring and cable sizes must comply with your particular country’s wiring regu-
lations and Codes of Practices. Ensure that suitable disconnection devices and
RCDs are fitted.
GEN/AUX
Generator connection.
GRID
This works like a conventional grid-tied inverter. It is both an input and
output connection for non-essential load and supply
LOAD
Connection of essential loads such as lighting, security systems, and
Internet
Before connecting to grid, please install a separate AC breaker between inverter and grid.
Also, it is recommended that installs an AC breaker between backup load and inverter.This will
ensure the inverter can be securely disconnected during maintenance and fully protected from
over current. For the 8KW model, the recommended AC breaker for backup load is 63A.
For the 8KW model, the recommended AC breaker for grid is 63A.
There are three terminal blocks with “Grid” “Load”and “GEN” markings. Please do not miscon-
nect input and output connectors.
Page | 21
Hybrid Inverter | Installer Manual
Summary of Contents for SUNSYNK-8K-SG01LP1
Page 9: ...2 1 Product Size Page 9 Hybrid Inverter Installer Manual Inverter Size...
Page 16: ...Page 16 Hybrid Inverter Installer Manual 4 5 Function Port Definition...
Page 20: ...Page 20 Hybrid Inverter Installer Manual...
Page 22: ...Page 22 Hybrid Inverter Installer Manual 4 9 1 Recommended AC Surge Protector...
Page 28: ...Page 28 Hybrid Inverter Installer Manual 4 13 Wiring System for Inverter...
Page 29: ...Page 29 Hybrid Inverter Installer Manual...
Page 34: ...03 02 01 Page 34 Hybrid Inverter Installer Manual...
Page 37: ...Page 37 Hybrid Inverter Installer Manual 4 19 2 Connected to a Generator 03 02 01...