User Manual
25
AC Circuit Breaker
An independent two-pole circuit breaker is installed on the output side of the
inverter to ensure safe disconnection from the grid. The recommended
specifications are as follows:
Inverter Model
Specification
SG2K-S / SG2K5-S
15 A
SG3K-S / SG3K-D
20 A
SG5K-D
32 A
SG8K-D
50 A
Multiple inverters cannot share one circuit breaker.
Never connect a load between the inverter and the circuit breaker.
Residual Current Device
With an integrated universal current-sensitive residual current monitoring unit
inside, the inverter will disconnect immediately from the mains power once a
fault current with a value exceeding the limit has been detected.
If an external residual current device (RCD) is strictly required, install a residual
current device (type A) which trigs at a residual current of 30 mA or higher.
5.5.2 Assembling the AC Connector
1.
Lead the AC cable through the
cable gland and the housing.
2.
Remove the cable jacket by
40 mm, and strip the wire
insulation by 8-15 mm.
8-15 mm
PE
L
N
40 mm