Tab. 7-5
“
Volt-watt
” Mode Parameter Explanations
Parameter
Explanation
Default
Range
AU
NZ
V1 Ref.
Grid voltage reference
value 1
207.0 V
207.0 V
Not applicable
V2 Ref.
Grid voltage reference
value 2
220.0 V
220.0 V
216 V–230 V
V3 Ref.
Grid voltage reference
value 3
250.0 V
244.0 V
235 V–255 V
V4 Ref.
Grid voltage reference
value 4
265.0 V
255.0 V
244 V–265 V
The response curve is defined by the voltage reference values and
corresponding power levels.
Power
,
P
/P
rated
%
200
Inverter Voltage, V
V2
V3
V4
210
220
230
240
250
260
270
40%
60%
20%
80%
0%
V1
100%
Default characteristic
Range (lower limit)
Range (upper limit)
Fig. 7-2
Volt-watt Response Curve (“AU” for example)
Grid Protection Voltage Adjusting
All Sungrow’s inverters are compliant with the standard AS/NZS 4777 related to
grid protection requirements. In order to work with unstable utility grids,
inverters are equipped with automatic protection voltage adjusting function
(disabled by default). This mode can be enabled via the LCD.
OFF
(default setting)
:
the function is disabled. The grid protection voltage
cannot automatically adjust.
ON:
enables the protection function. The inverter will automatically adjust the
protection threshold to a higher value so as to be normally connected to the grid
in the event of grid over-voltage. The
V
max-rec
will be adjusted the same with the
V
max
, with an upper limit value not higher than V
max
.
If the setting is changed from
ON
to
OFF
, you should
set the protection voltage as specified in
according to local protection requirements.
OFF
ON