77
Parameter
Explanation
Range
QP_
EnterVoltage
Voltage percentage for Q(P) function
activation
100% ~ 110%
QP_ExitVoltage
Voltage percentage for Q(P) function
deactivation
90% ~ 100%
QP_ExitPower
Power percentage for Q(P) function
deactivation
1% ~ 100%
QP_EnableMode
Unconditional activation/deactivation of Q
(P) function
Yes / No
QU_Limited PF
Value
PF value for Q(U) function activation
0~1
* Curve C is reserved and consistent with Curve A currently.
figure 7-19
Q(P) Curve
table 7-13 “Q(U)” Mode Parameter Descriptions:
Parameter
Explanation
Range
Q(U) curve
Select corresponding curve according to lo-
cal regulations
A, B, C
*
Hysteresis Ratio
Voltage hysteresis ratio on the Q(U) mode
curve
0 ~ 5%
QU_V1
Grid voltage limit at P1 on the Q(U) mode
curve
80% ~ 100%
QU_Q1
Value of Q/Sn at P1 on the Q(U) mode
curve
-60% ~ 0
QU_V2
Grid voltage limit at P2 on the Q(U) mode
curve
80% ~ 100%
QU_Q2
Value of Q/Sn at P2 on the Q(U) mode
curve
-60% ~ 60%
QU_V3
Grid voltage limit at P3 on the Q(U) mode
curve
100% ~ 120%
QU_Q3
Value of Q/Sn at P3 on the Q(U) mode
curve
-60% ~ 60%