5.8.5.2 Wiring Procedure
For detailed connection description of the DI/DO cable, refer to the section
. Plug the wires into the
DI/DO
terminal according the labels on the bottom of
the inverter.
5.8.6 DRM Connection
DRM and Ripple Control support only one function at the same time.
DRM
In Australia and New Zealand, the inverter supports the demand response modes as
specified in the standard AS/NZS 4777.
The following figure shows the wiring between the inverter and the external DRED.
table 5-5 Method of Asserting DRM
Mode
Asserted by Shorting Terminals
on Inverter
Switch Operation on External
DRED
DRM0
R & C
Close S1 and S5
Enable the DRM function through the iSolarCloud APP. If there are any problems,
contact your distributor first. If the problem persists, contact SUNGROW.
The DRM function is only applicable to devices for Australia and New Zealand.
Ripple Control
In Germany, the grid company uses the Ripple Control Receiver to convert the grid
dispatching signal and send it as a dry contact signal.
Wiring of the ripple control receiver dry contact cables is shown in the figure below: