19
The distance from the bottom of the inverter to the ground is determined according
to the bending radius of the selected AC cable and the installation environment,
and the following requirements should be met
:
•
The distance from the bottom of the inverter to the ground should be ≥ 650mm.
•
The AC cable should be connected to the AC terminal vertically, and the length
of the vertical cable should be ≥ 200mm.
Contact the AC cable manufacturer for any questions.
In case of multiple inverters, reserve specific clearance between the inverters.
Back-to-Back Installation
When installing inverters back-to-back, the distance between every two inverters should be
at least 200 mm.
Add a baffle between the two inverters to form a heat dissipation channel. The baffle plate
should be placed horizontally between two inverters and should not block the air outlet of
inverters.
User Manual