Overview of Electrical Connection
Electrical connections of the inverter include DC connection, AC connection and
communication connection.
This should comply with the National Wiring Rules of Standard AS/NZS 3000.
The requirements in AS 4777.1 and AS/NZS 3000 indicate that a DC isolator must be
used before the inverter.
Fig 5-2 Electrical Connection Diagram
Item Description
Remark
A
PV arrays
The maximum open-circuit voltage of each PV string is 450V.
B
SolarInfo
logger
It can be ordered from Sungrow.
C
Remote PC
User uses this device to monitor the whole PV system.
D
AC circuit
breaker
Used as a protective device during electrical connection. User equips
this device according to maximum output voltage and current.
E
Utility Grid
Grid voltage is 230V.