51
When the current transformer is set to "External", set current transformer parameters
according to the following
table 7-13 Parameter description of external current
table 7-13
Parameter description of external current transformer
P
Pa
arra
am
me
ette
err
D
De
effa
au
ulltt vva
allu
ue
e
R
Ra
an
ng
ge
e
Current transformer output current
5A
-
Current transformer measuring range
200A
1 ~ 10000A
If an Smart Energy Meter equipped with external current transformer is
applied, the measurement range (primary current) of the current transformer
should be selected according to actual maximum current at the grid-
connected point, and the maximum secondary current (output current) of the
current transformer should be 5A.
The current transformer’s primary current should be equal to or greater than
the maximum expected AC current from the grid, per phase. Important: The
closer the expected AC current is to the chosen primary current value, the
more precise the measurement will be.
User Manual