AWG Wire Sizes
AWG gauge
Conductor
Diameter Inches
Conductor
Diameter mm
OOOO
0.46 11.684
OOO
0.4096 10.40384
OO
0.3648 9.26592
0
0.3249 8.25246
1
0.2893 7.34822
2
0.2576 6.54304
3
0.2294 5.82676
4
0.2043 5.18922
5
0.1819 4.62026
6
0.162 4.1148
7
0.1443 3.66522
8
0.1285 3.2639
9
0.1144 2.90576
10
0.1019 2.58826
11
0.0907 2.30378
12
0.0808 2.05232
13
0.072 1.8288
14
0.0641 1.62814
15
0.0571 1.45034
16
0.0508 1.29032
When connecting the inverter to the power source, it is recommended to use the largest diameter
wire available in the shortest length possible.
The table below recommends the AWG Wire size for each inverter not to exceed .2 volts loss in
the cables connected to the inverter when it is operated at Maximum capacity.
See the Table below for recommendations
1000w unit
distance from battery
AWG Gauge
2ft
4
4ft
4
6ft
3
10ft
0
2500w unit
distance from battery
AWG Gauge
2ft
3
4ft
1
6ft
0
10ft
0000
4500w unit
distance from battery
AWG Gauge
2ft
1
4ft
000
6ft
0000
10ft
N/R