Hysteresis  of  minimum  operating  temperature  introduces  a  tolerance  for  the  activation  threshold  temperature 
preventing

 

unwanted oscillations at activation low temperature fluctuations. This is the difference between the heat 

pump activation

 

temperature and the temperature of its deactivation (after the temperature drop).

Example: when the minimum operating temperature is set to 5

°

C and the hysteresis is set at 2

°

C, the heat pump 

activates at

 

5

°

C, but when the temperature drops to a value of 3

°

C the pump is deactivated.

The user can decide whether the heater is to be enabled below the minimum air temperature.

This option is used to set the tank temperature hysteresis. This is the difference between the set point temperature 
(desired on a

 

boiler - when the heat pump turns off) and a temperature of the heat pump return to work.

The ECO - ECO PLUS threshold is a tank temperature at which the generator is turned off and further tank post heating 
starts

 

to be carried out using the heater or/and an additional heat source.

This option is used to set the temperature hysteresis for the ECO - ECO PLUS threshold (disconnection of the unit and 
the

 

engagement of an additional heat source), in order to prevent unnecessary oscillations. This is the difference 

between the

 

temperature of threshold disengagement of the generator and the temperature of the generator return to 

work (after the

 

temperature drop below the ECO - ECO PLUS threshold).

The operation of the installation protection depends on the pressure switch (the pressure sensor).

 

In the event of the engagement of this function, the signal of the pressure switch with too high pressure disables the 
pump and

 

triggers the alarm.

The emergency temperature is a parameter protecting the compressor and the generator from overheating. In the 
event of a

 

dangerous increase in the temperature of the control sensor (up to an emergency temperature) 3 times within 

an hour the

 

generator disengages permanently. In this case the restart of the device is only possible via the heat pump 

manufacturer

 

service.

After starting the heat pump, first engages the ventilator and the pump, and then after a few seconds, the compressor. 
This

 

setting adjusts the time delay of the compressor engagement after the ventilator and the pump. When the pump is 

about to

 

disengage (e.g.: the ECO - ECO PLUS threshold temperature is to be reached), first the compressor is 

disengaged and after a

 

set time delay, the ventilator and the pump.

This parameter is closely linked with the emergency temperature function. If the control temperature exceeds the 
emergency

 

threshold 3 times within an hour, it is possible to heat only with the heater.

Using this setting it is possible to edit the service phone number, which is displayed in the user menu: Information. Set 
the

 

desired value by turning the encoder, accept the choice by pressing the encoder.

With this function you can change the access code to the service menu. Set the desired value by turning the encoder, 
accept the

 

choice by pressing the encoder.

The controller is pre-configured to work. However, it should be adjusted to your needs. You can return to the factory 
settings

 

at any time. When enabling the option of factory settings all custom settings of the heat pump are lost (stored in 

user menu) to

 

the settings stored by the controller manufacturer. From this point you can re-set your own service 

parameters of the heat

 

pump.

5.12 

Hysteresis of minimum operating temperature

5.13 

Heater operation below minimum operating temperature

5.13.1 

Hysteresis of set point temperature

5.13.2 

ECO-ECO PLUS threshold temperature

5.13.3 

Hysteresis of ECO-ECO PLUS threshold

5.14 

Installation protection

5.15 

Emergency temperature

5.16 

Delay compressor

5.17 

Clear alarm of control temperature

5.18 

Edit service phone number

5.19 

Change service code

5.20 

Factory settings

-12-

Summary of Contents for DROPS D4.1

Page 1: ...DROPS D4 1 Air Water Heat Pump Operating manual and assembly Version 1 2 19012017 Effect from serial number 164010111 ...

Page 2: ......

Page 3: ...n 11 5 9 LEGIONELLA settings 11 5 9 1 LEGIONELLA temperature 11 5 9 2 LEGIONELLA duration 11 5 9 3 Maximum LEGIONELLA time 11 5 9 4 LEGIONELLA reminder 11 5 10 Evaporator defrost 11 5 11 Minimum operating temperature 11 5 12 Hysteresis of minimum operating temperature 12 5 13 Heater operation below minimum operating temperature 12 5 13 1 Hysteresis of set point temperature 12 5 13 2 ECO ECO PLUS t...

Page 4: ... also to work directly with utility water The correct operation of the heat pump is ensured by the controller with algorithm optimized for the heat pump DROPS D4 1 construction The housing is made of ABS plastic All the above mentioned characteristics components comprise the high quality and efficiency of the heat pump Any operations not described in this manual must be carried out in accordance w...

Page 5: ... between the heat pump and the storage tank must have an internal diameter of 20 mm On the water return to the heat pump pipeline install an angled filter The pipelines should be isolated on the whole length The heat pump has two connectors for connecting the air ducts The internal diameter of the air ducts must be min 200mm The maximum lengths of the air tubes 8m In case of connecting air ducts o...

Page 6: ...NTERNAL ROOM 1 INTERNAL ROOM 2 AIR ABSORBED FROM OUTSIDE THROUGH WALL AND DISCHARGED OUTSIDE THROUGH WALL OUTSIDE AIR OUTSIDE AIR OUTSIDE AIR OUTSIDE AIR AIR SUPPLIED TO 3 ROOMS 150 250 m h AIR DISCHARGED FROM ROOMS Heat pump and recuperative central are working independently of another one so that s why air ducts also should be separated The point is that in time when recuperative is working but ...

Page 7: ...ualifications 3 5 Electrical connection 3 6 Installation diagram 4 Description of controller functions 7 HEATER VENTILATOR COMPRESSOR TANK PUMP HIGH PRESSURE SWITCH LOW PRESSURE SWITCH SG SWITCH EXTERNAL SENSOR TANK SENSOR CONTROL SENSOR EVAPORATOR SENSOR DEFROST VALVE CIRCULATION PUMP 1 5 4 3 2 6 7 8 9 10 11 12 13 14 1 Evaporator temperature 2 External temperature 3 Control temperature 4 Enter th...

Page 8: ...nt date The function allows you to define the brightness of the display during the edit and view of the controller functions in the range of 10 100 The function allows you to define the brightness of the display during the dimming which is activated in 30 seconds after the end of the edit and view of the controller functions in the range of 5 100 The function allows you to preview the controller i...

Page 9: ...want to clarify the individual settings By turning the encoder the user can select one of the following days of the week all day Entire week working days or weekends Saturday and Sunday The next step is to select the hours in which the pump has to run in reduced mode and in which in comfort mode By turning the encoder move over an hour the setting you want to change and press the encoder The scree...

Page 10: ... Final evaporator temperature External temperature Maximum defrost duration Minimum operating temperature Hysteresis of minimum operating temperature Heater operation below minimum operating temperature Hysteresis of set point temperature ECO ECO PLUS threshold temperature Hysteresis of ECO ECO PLUS threshold Installation protection Emergency temperature Delay compressor Clear alarm of control tem...

Page 11: ... service tab Defrost is limited in time by the max defrost duration parameter If during this time the evaporator cannot be effectively defrosted the heat pump switches to the 10 minute pre heating cycle and then again a process of defrosting After 3 unsuccessful attempts of defrosting the defrost error message is displayed The heat pump is locked All the protection functions remain active The heat...

Page 12: ...se in the temperature of the control sensor up to an emergency temperature 3 times within an hour the generator disengages permanently In this case the restart of the device is only possible via the heat pump manufacturer service After starting the heat pump first engages the ventilator and the pump and then after a few seconds the compressor This setting adjusts the time delay of the compressor e...

Page 13: ...reeing any of the pressure switches cause stop working of circulation pump and appearance sound signal Additional air compressor is safed by the sensor of hot gas The heat pump DROPS D4 1 was designed to work with the installations of photovoltaic panels and operating in energy tariffs The controller has an additional potential free NO contact After triggering the contact the heat pump and HUW tan...

Page 14: ...UW TO INLET Ø200 1 HEAT PUMP 2 BALL VALVE 3 CIRCULATION PUMP 4 CHECK VALVE 5 DIAPHRAGM PRESSURE EXPANSION VESSELS 6 SECURITY VALVE 7 HUW TANK 8 SECURITY VALVE 9 DIAPHRAGM PRESSURE EXPANSION VESSELS 10 INLET STRAINER TO OUTLET Ø200 CW ...

Page 15: ... 15 CHUW HUW TO INLET Ø200 TO OUTLET Ø200 1 HEAT PUMP GELBI 2 BALL VALVE 3 CIRCULATION PUMP 4 CHECK VALVE 5 DIAPHRAGM PRESSURE EXPANSION VESSELS 6 SECURITY VALVE 7 HUW TANK 8 INLET STRAINER CW ...

Page 16: ... 16 10 1 Refrigerant circuit illustration ...

Page 17: ...trical parametres Recommended security COP water heating 10 40 C COP water heating 10 45 C COP water heating 10 50 C COP water heating 10 55 C Heating time for 100 L water at 10 40 C Heating time for 100 L water at 10 45 C Heating time for 100 L water at 10 50 C Heating time for 100 L water at 10 55 C Maximum heating capacity for drawn air temperature of 20 C Average heating capacity for drawn air...

Page 18: ...r 100 L water at 10 55 C Maximum heating capacity for drawn air temperature of 35 C Average heating capacity for drawn air temperature of 35 C and water heating from 10 to 55 C Energy consumption for drawn air temperature of 35 C A A A W W C6 min 0 29kW max 0 65kW 2 57 kW 1 9 kW 6 9 6 6 5 7 4 9 1 5h 1 9h 2 6h 3 4h Max starting electricity of the heat pump Max work electricity of the heat pump Powe...

Page 19: ...p signature of dealer Stamp signature of installing company Signature of investor Diagram no Other Start up protocol of the heat pump DROPS D4 1 Condensate drainage method Electrical connection Name and surname of the person performing Overcurrent Protection Residual current device Cross section of the power cord Heater Yes No Circulation pump Yes No Notes Start up date Note the temperature of the...

Page 20: ... 20 ...

Page 21: ...tor Name and surname of the actuating person Place of installation e g cellar Air ducts Diameter Material Heating pipeline Diameter Material Heating diagram corresponding with the operating instructions HUW tank capacity Feed temp heat pump Return temp heat pump Diagram no Other Condensate drainage method Electrical connection Name and surname of the person performing Overcurrent Protection Residu...

Page 22: ... 22 ...

Page 23: ... 23 ...

Page 24: ......

Reviews: