Preparing for Installation
1-13
1
1.5.3 Environmental Requirements
The acceptable environmental ranges for the SPARCserver 1000 system are:
•
Temperature between 32—104
°
Fahrenheit (0—40
°
Celsius)
•
With tape drive, the range is <>
°
Fahrenheit (5 - 40
•
Humidity between 5- and 80 percent (relative noncondensing)
•
With tape drive, lower limit is 20%
•
Altitude between 0- 10,000 feet (0 and 3048 meters) above sea level
•
Well-ventilated or air-conditioned work area to avoid overheating
•
Relatively dust-free (as in an office environment)
1.6 Site Preparation
1.6.1 Preparing Electrical Circuits
Your SPARCserver 1000 system uses nominal input voltages of 115 VAC or
230 VAC. Sun™ products are designed to work with single-phase power
systems having a grounded neutral conductor.
To reduce the risk of electrical shock, do not plug Sun products into another
type of power source. Contact your facilities manager or a qualified electrician
if you are unsure what type of power is supplied to your building.
In planning where to place your equipment, remember that each item below
requires access (by way of a separate power cord) to a power outlet:
•
SPARCserver 1000 system
+12 VDC
0 to 2.5A
–12 VDC
0 to 0.6A
+12 VDC
1.5 to 8A For peripherals and fans
Output
power rating
Total power not to
exceed
650W
Table 1-5
Power Supply Characteristics
Parameter
Value
Summary of Contents for SunSwift SPARCserver 1000
Page 6: ...vi SPARCserver 1000 System Installation Manual June 1996 ...
Page 10: ...x SPARCserver 1000 System Installation Manual June 1996 ...
Page 30: ...1 16 SPARCserver 1000 System Installation Manual June 1996 1 ...
Page 54: ...A 10 SPARCserver 1000 System Installation Manual June 1996 A ...
Page 68: ...SPARCserver 1000 System Installation Manual June 1996 ...