Operation manual of SR528Q wireless controller
- 28 -
collector rises up to EMOF limited temperature, solar circuit pump is ceased, but when
collector temperature drops to the collector maximum switch-on temperature EMON
(
factory
set is 120
o
C
)
, solar circuit pump will be recovery, and collector emergency close function
is deactivated.
Setup steps:
To access main menu TEMP, then select submenu EMOF
, “EMOF 130
o
C” shows on the
screen
►
Press
“Set” button, parameter “130
o
C” blinks.
►Press
“▲ ▼
” button, to adjust this maximum
switch-off temperature, adjust range (ON+3
o
C
)~
200
o
C, factory set is 130
o
C
►Repress “Set” button to activate and deactivate this function, if deactivate the function,
“EMOF - - -” shows on the screen.
► Press “Esc” button to exit menu or wait for 20 seconds to exit automatically, set
parameters are saved automatically.
6.4.2 EMON Maximum switch-on temperature of collector (for collector
emergency close function)
Setup steps:
To access main menu TEMP, then select submenu EMON
, “EMON 120
o
C” shows on the
screen
►Press “Set” button, parameter “120
o
C” blinks.
►Press
“▲ ▼
” button, to adjust this maximum
switch-on temperature, adjust range 60
o
C ~ (OF-3
o
C), factory set is 120
o
C
►Repress “Set” button to activate and deactivate this function, if deactivate the function,
“EMON - - -” shows on the screen.
► Press “Esc” button to exit menu or wait for 20 seconds to exit automatically, set
parameters are saved automatically.
When these 2 signs of collector emergency close function blink on the
screen, it indicates the function is activated, and tank temperature reaches up to its
maximum limitation.
When only this sign
of collector emergency close function
blinks on the screen, it
indicates the function is also activated, but temperature of tank doesn
’t reach to its