14. Do not connect to any furnace that is not equipped 

with an air circulation blower.

IT IS VERY IMPORTANT TO ADHERE TO THE MINI-

MUM INSTALLATION CLEARANCES TO ENSURE A 

SAFE INSTALLATION.

Installation

Before installation is started read and make sure that you 

understand these instructions.

1. Inspect unit to ensure that it has not been damaged in 

transit.

2. Remove electric controls and Instruction Envelope 

shipped inside firebox.

3. Install plenums and ductwork in accordance with Duct 

Diagram included in these instructions.

4. Do not connect duct work so that a reverse flow is 

possible.

5. “BX” type cable used for wiring between existing oil 

furnace and S-150 add-on, shall be installed with 1” 

“stand-offs” to prevent it from coming in contact with 

the S-150 casing.

6. The S-150 Summeraire add-on unit shall only be 

installed on a furnace duct system and chimney which 

are in good operating condition.

7. Do not use duct elbows having an inside radius of less 

than 6”.

8. Do not relocate or bypass any of the safety controls in 

the original furnace installation.

9. The blower in the oil or gas fired furnace shall not be 

changed.

10. To obtain the required air flow or temperature rise 

through the system, the blower and motor pulleys and 

the blower motor may have to be changed. Current 

flow through motor is to be maintained within name 

plate rating.

11. Install Limit Control Bracket as shown on assembled 

drawing using all holes provieded. Make sure this 

bracket is installed on the upper front of casing, fur-

thest from interconnecting duct. Install the prewired 

fan and limit Controls factory set at 280°F in hole 

provided nearest side of furnace and install fan and 

limit control Factory set at 200°F, in hole furthest from 

side of furnace regardless of right of left hand location 

of said mounting bracket.

12. Equipment shall be installed in a manner acceptable 

to the Regualatory Authority and only by mechanics 

experienced in such installations. When required by 

the Authority, such mechanics shall be licensed.

13. A separate thermostat must be installed and a new 

wire run to control this furnace.

Control Settings

Room Thermostat should be set in the 65°F to 70°F range.

Wood fan and limit control setting - 280°F (Factory Set)

Secondary oil limit control setting - 200°F (Factory Set)

Circulation fan blower off at 155°F (cuts in blower fan 

when temperature is reached).

Circualtion fan blower off at 110°F (blower fan cuts out 

when heat exchanger is cooled below this setting).

High limit cut out 280°F closes draft damper door when 

heat exchanger reaches this temperature. Draft at chimney 

should be between .05 and .08 inches water column.

The C.S.A. Certified Draft Regulator supplied must be 

installed and set at .06” W.C.

WARNING

: If the draft regulator setting of .06 W.C. is 

exceeded, it could cause a solid fuel fire to burn out-of-

control.

The damper door on the S-150 has an opening limited to 

1/2” by a tab and screw arrangement. This is the maxi-

mum that this furnace is designed to fire at. Any tamper

-

ing of this will cause an out-of-control fire.

After Installation Check

Turn on electrical power to the unit. Set thermostat below 

room temperature. The damper door should be shut.

Set thermostat higher than room temperature. Damper 

door should be open.

Push in the button on the Honeywell fan limit control and 

the circulation blower fan motor should come on. Return 

the button to the auto position for firing.

Summary of Contents for S150

Page 1: ...______________ S150 ADD ON FURNACE READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE OPERATING YOUR SUMMERAIRE FURNACE SAVE THESE INSTRUCTIONS FOR REFERENCE THIS FURNACE MUST BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER AND WHERE REQUIRED BY LAW A LICENCED TECHNICIAN SUMMERAIRE MFG PETERBOROUGH ONTARIO FOR SERVICE CALL INSTALLATION and OPERATING INSTRUCTIONS ...

Page 2: ...nt for tight structures or that required by C S A Standard CAN3 B365 installation code for solid fuel burning appliances equipment 8 CERTIFIED FOR SERIES CONNECTION TO THE OUTLET ONLY OF AN EXISTING OIL OR GAS FIRED FURNACE 9 If series method of interconnecting duct is used and the existing oil or gas furnace is equipped with plenum mounted fan limit control the divider panel which you install mus...

Page 3: ...0 F in hole provided nearest side of furnace and install fan and limit control Factory set at 200 F in hole furthest from side of furnace regardless of right of left hand location of said mounting bracket 12 Equipment shall be installed in a manner acceptable to the Regualatory Authority and only by mechanics experienced in such installations When required by the Authority such mechanics shall be ...

Page 4: ...nduct ed to minimize primary surface temperatures and ensure efficient air circulation Instructions for Control Wiring S 150 1 Mount prewired junction box and controls on wood furnace 2 Remove isolating relay from junction box 3 Run 3 wire 14 BX and 2 wire 14 BX from junction box on wood furnace to junction box on oil or gas furnace If BX wire is run along wood furnace casing it must have 1 stand ...

Page 5: ... Air Supply Air Flow Minimum Radius 6 Summeraire Energy Saver Model S150 Existing Furnace OIL or GAS Floor Level NOTE Minimum Plenum height for existing Oil Furnace 26 Minimum Duct Size 240 sq ins SERIES FLOW INSTALLATION METHOD ...

Page 6: ...6 Air Flow Minimum Radius 6 26 Minimum Plenum Height Summeraire Model S150 Energy Saver Minimum Duct Size 240 sq in Floor Level INLINE FLOW INSTALLATION METHOD Existing OIL or GAS Furnace ...

Page 7: ...ack Red White White Orange Isolating Relay To Gas Valve 24V Transformer 24V Gas Valve Fan Motor Damper Motor Gas Stat Wood Stat WIRING DIAGRAM FOR ADD ON TO GAS FURNACE ONLY NOTE Remove existing thermostat wires Hook these wires to terminals W R on Isolating relay Run a thermostat wire from TH TH on Gas Valve S 150 Summeraire ADD ON Furnace ...

Page 8: ...Junction Box 4X4 Junction Box on Wood Furnace Isolating Relay To Primary Control Damper Motor Oil Stat Wood Stat WIRING DIAGRAM FOR ADD ON TO OIL NOTE 1 Remove Black wire on oil primary control limit control wire and attach to new wires as shown 2 Remove existing thermostat wires Hook wires on terminals W R on isolating relay Run thermostat wire on T T on oil primary to T T on isolating relay FOR ...

Page 9: ...Codes and regulations NOTE If changes are made to the installation of a gas furnace including clearances for servicing these changes shall comply with CGA Standard CAN1 B149 1 or CAN1 B149 2 3 Oil furnace is to be installed to C S A Standard B 139 4 Owner is fully instructed in operating furnace and in all procedures necessary to ensure its complete and safe operation 5 The enclosed card must be f...

Page 10: ...er pulley arrangement Operate the oil fired or gas fired unit periodically to en sure that it will operate satisfactorily when needed Keep fire door closed and maintain all seals in good condition Make sure adequate combustion air is provided in furnace area The S 150 Add On is not to be used with an automatic stoker Firing Star the fire in your wood burning furnace with paper and kindling only Cr...

Page 11: ...be brushed out and discarded with the ash removed from the firebox Removal of ash and soot should only be necessary every few weeks but we recommend that to ensure a long life for the furnace you should have it thoroughly vaccum cleaned by your heating contractor as soon after the end of the heating season as possible Chimney cleaning should be done whenever any signifi cant soot and creosote buil...

Page 12: ...d is the size of the fuel charge along with the control of combustion air to increase or decrease the rate of burning which governs the heat output To help prevent creosote in both grate and base burners burn dry seasoned wood hard wood is more desirable than soft wood Govern your wood load with the heat output required Spring and fall require frequent small charges A small intense fire produces l...

Page 13: ... Warranty extends only to the repair or replacement of parts returned freightprepaid to our facilities in Peterbor ough Ontario and which prove defective after inspection and testing by us Any labour involved in diagnostics repair orreplacement is excluded from this warranty and Summeraire Mfg assumes no responsibil ity for consequential damages of any kind to persons or property The following for...

Page 14: ...14 F S150 INSMAN EN REV6 Summeraire Mfg 2040 Fisher Drive Peterborough Ontario Canada K9J 6X6 ...

Reviews: