4
When all these checks are O.K. you must now fire the
furnace following the operating instructions and check the
following:
Check that the circulation fan blower comes on when the
furnace reaches a temperature of 155°F.
Check that the damper door closes when the house
reaches the desired temperature.
Check that the blower fan motor shuts off when the fur-
nace temperature drops below 110°F.
When you have completed the intial start up tests and are
satisfied that the system is functioning properly you must
now fully explain the operating of the unit to your cus-
tomer. You must give your customer both the Installation
and Owner’s Operation Instructions and caution him as to
the safety practices which he must comply with.
Testing
All “Summeraire” furnaces are factory tested to ensure
reliability of welding; air streams tests have been conduct-
ed to minimize primary surface temperatures and ensure
efficient air circulation.
Instructions for Control Wiring S-150
1. Mount prewired junction box and controls on wood
furnace.
2. Remove isolating relay from junction box.
3. Run 3 wire #14 BX and 2 wire #14 BX from junction
box on wood furnace to junction box on oil or gas
furnace. If BX wire is run along wood furnace casing
it must have 1” stand off casing and plenum.
4. Wires in wood furnace aare colour coded to be run to
oil or gas furnace as follows:
A) Remove wire from oil or gas furnace limit con-
trol from black wire on oil primary control or gas
valve.
B) Blue wire in wood furnace hooks onto wire from
limit on oil or gas furnace.
C) Black wire in wood furnace hooks onto black
supply wire feeding oil or gas furnace.
D) Red wire in wood furnace hooks onto black wire
on oil primary control or gas valve.
E) White wire in wood furnace hooks onto white
supply wire in oil furnace or gas furnace.
F) Orange wire in wood furnace runs to load side or
fan control (Black wire) feeding fan motor.