background image

11

In a few days you will establish the basic recharging 

period for your specific application.

It is better to build small intense fires than building large 

smoldering fires as they reduce creosote build-up.

Ash Removal

A layer of ash approximately 1 1/2” deep should be left in 

the firebox at all times during the heating season to pro

-

tect the base of the firebox. When the ash bed accumualtes 

to a depth of 4” or 5”, or when accumulation interferes 

with responsive firing, proceed as follows:

1. Allow fire to burn out.

2. Turn off electrical power to the unit. This allows the 

damper door to close.

3. Remove ash with clean out tool provided, leaving a 1 

1/2” layer over the entire bottom of the firebox.

4. Ash is disposed of in a steel container with a tightly 

fitting lid and moved out of doors immediately. Other 

waste shall not be put in this container.

5. Check to ensure that the damper door shuts properly 

after cleaning to prevent any possibility of a run-away 

fire.

6. After ash removal return electric power to ON position 

and recharge fire.

Cleaning Unit

Periodically remove creosote, wood ash and soot accu-

mulation from flue passageways to ensure maximum heat 

transfer and to help prevent chimney fires. This is done 

with a scrapper and a flexible wire brush.

Cleaning of the firebox is done through the charging door. 

To clean flues and heat exchanger it will be necessary to 

remove the flue pipe and two clean out covers from front 

of unit.

The entire inside surface of the heat exchanger and flue 

will have to be scrapped of any excess creosote and all 

soot and ash will have to be brushed out and discarded 

with the ash removed from the firebox.

Removal of ash and soot should only be necessary every 

few weeks, but we recommend that, to ensure a long life 

for the furnace, you should have it thoroughly vaccum-

cleaned by your heating contractor as soon after the end 

of the heating season as possible.

Chimney cleaning should be done whenever any signifi

-

cant soot and creosote build up is noticed. A visual inspec-

tion of the chimney should be made whenever the furnace 

is cleaned.

FAILURE TO CLEAN THE CHIMNEY AND FLUES 

WILL RESULT IN A CHIMNEY FIRE!

Controls

The fan and limit controls, installed on your wood fur-

nace, have been set to activate the air circulation fan to 

start when the outlet air temperature reaches 155°F and 

shut off at 110°F, and close off damper door when the 

temperature reaches 280°F.

These settings should not be touched.

Gravity Firing Instruction

This unit has been designed to be safely fired using grav

-

ity circulation air. To fire this unit in the gravity fire mode, 

it is required to increase air circulation. This is accom-

plished by opening all registers fully, opening the furnace 

room door, removing panel on side of furnace opposite 

from where return air normally is forced into unit, (see 

exploded drawing included), removing the rear blower 

access panel of the oil or gas furnace. It is important to 

retard the firing rate in order to prevent over-heating of 

your furnace. To do this, close the draft damper door 

by unlocking the chain. The combustion air can now be 

supplied through the “peep hole” in the charging door. 

Further retard the fire by limiting the charge.

NEVER LOAD THE FIREBOX HIGHER THAN 1/4 OF 

THE WAY UP THE DOOR DURING GRAVITY FIRING

OPERATION. 

PLEASE NOTE: During gravity firing the furnace MUST 

BE ATTENDED REGULARLY.

Summary of Contents for S150

Page 1: ...______________ S150 ADD ON FURNACE READ AND UNDERSTAND THESE INSTRUCTIONS BEFORE OPERATING YOUR SUMMERAIRE FURNACE SAVE THESE INSTRUCTIONS FOR REFERENCE THIS FURNACE MUST BE INSTALLED AND SERVICED BY A QUALIFIED INSTALLER AND WHERE REQUIRED BY LAW A LICENCED TECHNICIAN SUMMERAIRE MFG PETERBOROUGH ONTARIO FOR SERVICE CALL INSTALLATION and OPERATING INSTRUCTIONS ...

Page 2: ...nt for tight structures or that required by C S A Standard CAN3 B365 installation code for solid fuel burning appliances equipment 8 CERTIFIED FOR SERIES CONNECTION TO THE OUTLET ONLY OF AN EXISTING OIL OR GAS FIRED FURNACE 9 If series method of interconnecting duct is used and the existing oil or gas furnace is equipped with plenum mounted fan limit control the divider panel which you install mus...

Page 3: ...0 F in hole provided nearest side of furnace and install fan and limit control Factory set at 200 F in hole furthest from side of furnace regardless of right of left hand location of said mounting bracket 12 Equipment shall be installed in a manner acceptable to the Regualatory Authority and only by mechanics experienced in such installations When required by the Authority such mechanics shall be ...

Page 4: ...nduct ed to minimize primary surface temperatures and ensure efficient air circulation Instructions for Control Wiring S 150 1 Mount prewired junction box and controls on wood furnace 2 Remove isolating relay from junction box 3 Run 3 wire 14 BX and 2 wire 14 BX from junction box on wood furnace to junction box on oil or gas furnace If BX wire is run along wood furnace casing it must have 1 stand ...

Page 5: ... Air Supply Air Flow Minimum Radius 6 Summeraire Energy Saver Model S150 Existing Furnace OIL or GAS Floor Level NOTE Minimum Plenum height for existing Oil Furnace 26 Minimum Duct Size 240 sq ins SERIES FLOW INSTALLATION METHOD ...

Page 6: ...6 Air Flow Minimum Radius 6 26 Minimum Plenum Height Summeraire Model S150 Energy Saver Minimum Duct Size 240 sq in Floor Level INLINE FLOW INSTALLATION METHOD Existing OIL or GAS Furnace ...

Page 7: ...ack Red White White Orange Isolating Relay To Gas Valve 24V Transformer 24V Gas Valve Fan Motor Damper Motor Gas Stat Wood Stat WIRING DIAGRAM FOR ADD ON TO GAS FURNACE ONLY NOTE Remove existing thermostat wires Hook these wires to terminals W R on Isolating relay Run a thermostat wire from TH TH on Gas Valve S 150 Summeraire ADD ON Furnace ...

Page 8: ...Junction Box 4X4 Junction Box on Wood Furnace Isolating Relay To Primary Control Damper Motor Oil Stat Wood Stat WIRING DIAGRAM FOR ADD ON TO OIL NOTE 1 Remove Black wire on oil primary control limit control wire and attach to new wires as shown 2 Remove existing thermostat wires Hook wires on terminals W R on isolating relay Run thermostat wire on T T on oil primary to T T on isolating relay FOR ...

Page 9: ...Codes and regulations NOTE If changes are made to the installation of a gas furnace including clearances for servicing these changes shall comply with CGA Standard CAN1 B149 1 or CAN1 B149 2 3 Oil furnace is to be installed to C S A Standard B 139 4 Owner is fully instructed in operating furnace and in all procedures necessary to ensure its complete and safe operation 5 The enclosed card must be f...

Page 10: ...er pulley arrangement Operate the oil fired or gas fired unit periodically to en sure that it will operate satisfactorily when needed Keep fire door closed and maintain all seals in good condition Make sure adequate combustion air is provided in furnace area The S 150 Add On is not to be used with an automatic stoker Firing Star the fire in your wood burning furnace with paper and kindling only Cr...

Page 11: ...be brushed out and discarded with the ash removed from the firebox Removal of ash and soot should only be necessary every few weeks but we recommend that to ensure a long life for the furnace you should have it thoroughly vaccum cleaned by your heating contractor as soon after the end of the heating season as possible Chimney cleaning should be done whenever any signifi cant soot and creosote buil...

Page 12: ...d is the size of the fuel charge along with the control of combustion air to increase or decrease the rate of burning which governs the heat output To help prevent creosote in both grate and base burners burn dry seasoned wood hard wood is more desirable than soft wood Govern your wood load with the heat output required Spring and fall require frequent small charges A small intense fire produces l...

Page 13: ... Warranty extends only to the repair or replacement of parts returned freightprepaid to our facilities in Peterbor ough Ontario and which prove defective after inspection and testing by us Any labour involved in diagnostics repair orreplacement is excluded from this warranty and Summeraire Mfg assumes no responsibil ity for consequential damages of any kind to persons or property The following for...

Page 14: ...14 F S150 INSMAN EN REV6 Summeraire Mfg 2040 Fisher Drive Peterborough Ontario Canada K9J 6X6 ...

Reviews: