background image

Note:

For pr

oper operation and maximum efficiency, the RIEL-

LO Burner must be set up exactly as shown on the
enclosed specification sheet. Settings for “Nozzle
Pressure”, “Burner Turbulator Setting”, and “Burner Air
Setting” are shown under each of 4 nozzle selections
that can be used with this furnace. Furnace is shipped
with .50 G.P.H. Nozzle installed and appropriate settings
made on burner to suit this nozzle size.

For complete detail regarding the Riello Burner, read
service manual enclosed with burner.

Fan Contr

ol

The setting of the fan contr

ol will depend upon the par-

ticular house and heating installation. The “Fan Off” set-
ting is factory set at 100 degrees F. This setting should
provide satisfactory operation for most installations. The
“Fan On” temperature is determined by the built in differ-
ential setting of the control.

It is desirable to have the “Fan Off” setting low enough
for extended blower operation. However, a “Fan Off” set-
ting too low will circulate cool air. To alter the “Fan Off”
setting rotate the indicator to the desired position on the
temperature scale.

Adjustments of all controls should only be made by a
competent serviceman. Control settings and blower
speed should be in accordance with the recommenda-
tions of the National Warm Air Heating and Air
Conditioning Association.

Summer Fan Operation

During the summer

, continuous air circulation can be

obtained by turning the manual fan switch from the
“auto” position to the “on” position.

Dual Air Operation

Fur

naces equipped with a dual speed blower system

enable partial air circulation at all times. When the ther-
mostat calls for heat the burner starts, and the high
speed phase quickly distributes warmed air throughout
the house. When the high speed phase ceases, the low
speed phase continues circulating the air to even tem-
peratures throughout the dwelling.

High Limit Contr

ol

The high limit contr

ol may be of a single switch type or

combination type in conjunction with the fan control. A
replacement limit control must be identical to that sup-
plied as original equipment.

Combustion Safety Contr

ol

Operation and checking of the primary contr

ol is outlined

in detail with the enclosed manufacturer literature.

Cleaning Pr

ocedure

Caution:

Do not use any commer

cially available soot remover. Use

extreme care when servicing since the combustion
chamber is fragile. Routine cleaning of the flue passages
does not require cleaning of the combustion chamber. If
for some reason it is necessary to work in the area of the
chamber do not touch or alter the chamber position.

Before cleaning, shut off electrical power supply to the
furnace.
Remove cleanout panel and cap from the front panel.
Loosen soot from the radiator with a cleaning tool or
brush. The tool should bend allowing cleaning around the
curved surfaces of the heat exchanger.

To clean the rear of the radiator remove the chimney flue
pipe from the furnace flue pipe.

Remove the flue baffle from the flue pipe. Loosen the
soot from the rear of the heat exchanger, flue pipe and
baffle.

Replacement Combustion Chamber

Should r

eplacing of chamber become necessary a spe-

cial replacement chamber is available.

Important -

When or

dering replacement combustion

chamber specify furnace model number.

Summary of Contents for RME 111

Page 1: ...OTE THIS FURNACE IS IN COMPLIANCE WITH THE CSA STANDARD B140 0 03 BLOCKED FLUE THEREFORE THE BLOCKED VENT SAFETY SWITCH MODEL WMO 1 SUPPLIED WITH THIS FURNACE MUST BE INSTALLED IN ACCORDANCE WITH THE INSTRUCTIONS INCLUDED WITH THE CONTROL AND MUST BE MOUNTED WITHIN 6 OF THE BREACH OF THE FURNACE POWER SIDEWALL VENTING SEE SPECIAL INSTRUCTIONS IN INSTRUCTION MANUAL FURNACE LABEL SUMMERAIRE MFG PETE...

Page 2: ... connecting to burner The oil line should be buried and protected by cement to eliminate any possible damage Installations having the fuel oil tank below the burner level must employ a two pipe fuel supply system with an appropriate fuel oil pump Installation of the furnace Location Locate the furnace as closely as possible to the chimney providing ample clearance to permit easy accessibility for ...

Page 3: ...eed blower system enable partial air circulation at all times When the ther mostat calls for heat the burner starts and the high speed phase quickly distributes warmed air throughout the house When the high speed phase ceases the low speed phase continues circulating the air to even tem peratures throughout the dwelling High Limit Control The high limit control may be of a single switch type or co...

Page 4: ... 50 65 75 85 INPUT U S G H 65 75 85 1 00 INPUT B T U H 90610 104550 118490 139400 OUTPUT B T U H 75000 86000 96000 111000 NOZZLE PRESSURE psig 120 135 130 140 BURNER TURBULATOR SETTING 1 0 1 5 3 0 3 0 BURNER AIR SETTING 3 0 3 2 3 8 6 0 TEMP RISE F 85 85 85 85 EXT S P 20 20 20 20 C F M 785 890 1015 1220 MOTOR H P 1 3 1 3 1 3 1 3 MOTOR PULLEY 3 1 4 X 1 2 3 1 4 X 1 2 3 1 4 X 1 2 3 1 4 X 1 2 BLOWER PU...

Page 5: ......

Page 6: ......

Page 7: ... for use with Tjernlund SS1 C power side wall ventor When RME 111 is installed with SS1 C side wall ventor use 20 AMP circuit protection The Restrictor Plate supplied MUST be installed in the 6 portion of the Flue Pipe See detailed installation instructions below See SS1C Instruction Book for complete installation instructions 3 Feet 6 Tapered Reducer Appliance Restrictor Plate Cut slot to suit re...

Page 8: ...nd serv iced at least once a year by a licenced burner mechanic As part of this annual service ensure the flue pipe s are cleaned inspected and if required they should be replaced How to start your oil furnace The operation of the oil burner is entirely automatic To start it set the room thermostat above room tempera ture The oil burner will start automatically If the burner fails to start check t...

Reviews: