Installation Tips

Minimum Duct Sizes in square inches

G.P.H.

Supply Air

Return Air

.65

8 x 18

8 x 21

.75

8 x 20

8 x 23

.85

8 x 22

8 x 25

1.00

8 x 24

8 x 28

Recommended minimum warm air plenum height 18” - 20”.

Set blower C.F.M. to obtain 85° F temperature rise through the unit.

Power Side W

all Venting

Model RME 111 is C.S.A. certified for use with Tjer

nlund SS1-C power side wall ventor.

When RME 111 is installed with SS1-C side wall ventor use 20 AMP circuit protection.

The Restrictor Plate supplied MUST be installed in the 6” portion of the Flue Pipe.
See detailed installation instructions below.
(See - SS1C Instruction Book for complete installation instructions).

3 F

eet

6”

Tapered Reducer

Appliance

Restrictor Plate

Cut slot to suit
restrictor plate

6” Flue Pipe

Section

7” Flue Outlet

and Barometric Size

Slide restrictor plate

into slot and fastener

with screw

Summary of Contents for RME 111

Page 1: ...OTE THIS FURNACE IS IN COMPLIANCE WITH THE CSA STANDARD B140 0 03 BLOCKED FLUE THEREFORE THE BLOCKED VENT SAFETY SWITCH MODEL WMO 1 SUPPLIED WITH THIS FURNACE MUST BE INSTALLED IN ACCORDANCE WITH THE INSTRUCTIONS INCLUDED WITH THE CONTROL AND MUST BE MOUNTED WITHIN 6 OF THE BREACH OF THE FURNACE POWER SIDEWALL VENTING SEE SPECIAL INSTRUCTIONS IN INSTRUCTION MANUAL FURNACE LABEL SUMMERAIRE MFG PETE...

Page 2: ... connecting to burner The oil line should be buried and protected by cement to eliminate any possible damage Installations having the fuel oil tank below the burner level must employ a two pipe fuel supply system with an appropriate fuel oil pump Installation of the furnace Location Locate the furnace as closely as possible to the chimney providing ample clearance to permit easy accessibility for ...

Page 3: ...eed blower system enable partial air circulation at all times When the ther mostat calls for heat the burner starts and the high speed phase quickly distributes warmed air throughout the house When the high speed phase ceases the low speed phase continues circulating the air to even tem peratures throughout the dwelling High Limit Control The high limit control may be of a single switch type or co...

Page 4: ... 50 65 75 85 INPUT U S G H 65 75 85 1 00 INPUT B T U H 90610 104550 118490 139400 OUTPUT B T U H 75000 86000 96000 111000 NOZZLE PRESSURE psig 120 135 130 140 BURNER TURBULATOR SETTING 1 0 1 5 3 0 3 0 BURNER AIR SETTING 3 0 3 2 3 8 6 0 TEMP RISE F 85 85 85 85 EXT S P 20 20 20 20 C F M 785 890 1015 1220 MOTOR H P 1 3 1 3 1 3 1 3 MOTOR PULLEY 3 1 4 X 1 2 3 1 4 X 1 2 3 1 4 X 1 2 3 1 4 X 1 2 BLOWER PU...

Page 5: ......

Page 6: ......

Page 7: ... for use with Tjernlund SS1 C power side wall ventor When RME 111 is installed with SS1 C side wall ventor use 20 AMP circuit protection The Restrictor Plate supplied MUST be installed in the 6 portion of the Flue Pipe See detailed installation instructions below See SS1C Instruction Book for complete installation instructions 3 Feet 6 Tapered Reducer Appliance Restrictor Plate Cut slot to suit re...

Page 8: ...nd serv iced at least once a year by a licenced burner mechanic As part of this annual service ensure the flue pipe s are cleaned inspected and if required they should be replaced How to start your oil furnace The operation of the oil burner is entirely automatic To start it set the room thermostat above room tempera ture The oil burner will start automatically If the burner fails to start check t...

Reviews: