background image

Installation Instructions

Summeraire Model - RME 111

This fur

nace is to be installed by a qualified technician.

Some jurisdictions may require the installer to be
licenced.

General

Installation of oil fir

ed heating units shall be in accor-

dance with the regulations of authorities having jurisdic-
tion and the current edition of CSA B139 installation
code for oil burning equipment.
The units are approved for fuel not heavier than No. 2
(furnace) oil. Do not use gasoline, crankcase oil, or any
oil containing gasoline.

Draft and Chimney Requir

ements

The chimney must be capable of pr

oducing a draft of

0.02 inches of water at the furnace flue pipe when the
unit is firing. The chimney should have a minimum height
of 20 feet and have nominal flue area dimensions of 8 x 8
inches. The chimney top should be at least 3 feet above
the point where it comes through the roof and must
extend two feet higher than any roof point within 10 feet.
In the case of a chimney which has been used previously
it is necessary to clean the flue before installing another
furnace.

Note: Due to the very high efficiency of the Riello Burner,
very low stack temperatures may be experienced.
Therefore, we recommend the lining of your chimney with
an approved flexible chimney liner.

Oil T

ank and Piping

Maximum capacity of individual tanks used shall be 250

gallons and must be located at least 7 feet from the
burner. Local codes will govern the size of vents and
fillers as well as the type of caps used. 1 1/4 inches IPS
and 2 inches IPS are generally accepted as minimum
sizes for vent and fill pipes respectively. The burner oil
line shall not be less than 3/8 inches O.D. copper tubing
for runs of 50 feet or less and 1/2 inches O.D. copper
tubing for longer runs. A manual shut off valve and an oil
filter shall follow in sequence from tank to burner. Be
sure that the oil line is clean before connecting to burner.
The oil line should be buried and protected by cement to
eliminate any possible damage. Installations having the
fuel oil tank below the burner level must employ a two
pipe fuel supply system with an appropriate fuel oil
pump.

I

nstallation of the fur

nace

Location

Locate the fur

nace as closely as possible to the chimney,

providing ample clearance to permit easy accessibility for
cleaning the inside of the furnace, the removal of filters,
blower, motors, controls and flue connections.

Combustion Air

In installations wher

e the furnace is located in a small

room at least one square foot of air opening per gallon
per hour of oil burner capacity must be provided at both
the top and the bottom of the furnace room door. These
openings ensure an adequate supply of combustion air
to the burner.

Positioning The Unit

The fur

nace must be level in both directions for safe

quiet operation. Support each vee runner equally for uni-
form weight distribution.

Flue Connection and Draft Regulator

The connecting pipe fr

om the furnace to the chimney

should be short and as straight as possible. The draft
regulator supplied with the unit must be installed in a
straight length of pipe no more than 18 inches from the
furnace flue exit pipe.

Wiring

All wiring fr

om the service panel to this furnace shall be

made in accordance with the Canadian Electrical Code
and must also comply with all local ordinances.

Filters

The fur

nace should never  be operated without filters.

This is especially true when temporary heat is required
during construction. In addition to permitting circulation
of dust and other suspended particles there is a possibil-
ity of bearing failure resulting from these foreign materials
in the blower and motor housings. Clean or replace filters
once each heating season.

Note:

A dirty filter causes inef

ficiency and higher operat-

ing costs.

Bur

ner Installation

Make sur

e your read and understand the enclosed

Burner Manual.
Install the burner to the pouch plate with the gasket pro-
vided.
No adjustment may be made to the burner mounting
position.

Summary of Contents for RME 111

Page 1: ...OTE THIS FURNACE IS IN COMPLIANCE WITH THE CSA STANDARD B140 0 03 BLOCKED FLUE THEREFORE THE BLOCKED VENT SAFETY SWITCH MODEL WMO 1 SUPPLIED WITH THIS FURNACE MUST BE INSTALLED IN ACCORDANCE WITH THE INSTRUCTIONS INCLUDED WITH THE CONTROL AND MUST BE MOUNTED WITHIN 6 OF THE BREACH OF THE FURNACE POWER SIDEWALL VENTING SEE SPECIAL INSTRUCTIONS IN INSTRUCTION MANUAL FURNACE LABEL SUMMERAIRE MFG PETE...

Page 2: ... connecting to burner The oil line should be buried and protected by cement to eliminate any possible damage Installations having the fuel oil tank below the burner level must employ a two pipe fuel supply system with an appropriate fuel oil pump Installation of the furnace Location Locate the furnace as closely as possible to the chimney providing ample clearance to permit easy accessibility for ...

Page 3: ...eed blower system enable partial air circulation at all times When the ther mostat calls for heat the burner starts and the high speed phase quickly distributes warmed air throughout the house When the high speed phase ceases the low speed phase continues circulating the air to even tem peratures throughout the dwelling High Limit Control The high limit control may be of a single switch type or co...

Page 4: ... 50 65 75 85 INPUT U S G H 65 75 85 1 00 INPUT B T U H 90610 104550 118490 139400 OUTPUT B T U H 75000 86000 96000 111000 NOZZLE PRESSURE psig 120 135 130 140 BURNER TURBULATOR SETTING 1 0 1 5 3 0 3 0 BURNER AIR SETTING 3 0 3 2 3 8 6 0 TEMP RISE F 85 85 85 85 EXT S P 20 20 20 20 C F M 785 890 1015 1220 MOTOR H P 1 3 1 3 1 3 1 3 MOTOR PULLEY 3 1 4 X 1 2 3 1 4 X 1 2 3 1 4 X 1 2 3 1 4 X 1 2 BLOWER PU...

Page 5: ......

Page 6: ......

Page 7: ... for use with Tjernlund SS1 C power side wall ventor When RME 111 is installed with SS1 C side wall ventor use 20 AMP circuit protection The Restrictor Plate supplied MUST be installed in the 6 portion of the Flue Pipe See detailed installation instructions below See SS1C Instruction Book for complete installation instructions 3 Feet 6 Tapered Reducer Appliance Restrictor Plate Cut slot to suit re...

Page 8: ...nd serv iced at least once a year by a licenced burner mechanic As part of this annual service ensure the flue pipe s are cleaned inspected and if required they should be replaced How to start your oil furnace The operation of the oil burner is entirely automatic To start it set the room thermostat above room tempera ture The oil burner will start automatically If the burner fails to start check t...

Reviews: