3
SRL
--
1200 --- SRL
--
6000 (60Hz)
English
5
Control
5.1
Control panel
4
5
2
1
3
y
x
é
z
è
[
&
Display
Reference
Name
Description
1
MAIN SWITCH
I ON = dryer powered;
O OFF = dryer not powered.
2
POWER LED
Yellow = dryer powered.
2
POWER LED
Green = Dryer operating.
3
ENERGY SAVING
LED
Lit = Dryer in energy saving
condition.
4
WARNING LED
Off = no signal.
4
WARNING LED
Flashing = Alarm or warning.
5
DRAIN LED
Lit = Drain open.
Keypad mode
STANDARD
MENU*
x
ON/OFF BUTTON
Switching on/off
Confirm
z
RESET BUTTON
Reset alarm/ warning
Up
é
HISTORY BUTTON
Alarm/warning log
Down
y
DRAIN BUTTON
Condensate drain
Out
* returns to STANDARD mode after 5 minutes.
5.2
Operation
Operation status
With the MAIN SWITCH
&
turned to “I ON” (dryer pow-
ered) three working conditions are possible:
DRYER
STATUS
[
DISPLAY
POWER LED (2)
1
OFF
Off
Yellow
2
ON
Dew point
Green
3
REMOTE OFF
r.OF
Yellow
To switch from OFF to ON (and vice versa) press
x
.
!
In OFF status the unit remains powered until the MAIN
SWITCH
&
is turned to “O OFF”!
Y
To manage REMOTE OFF mode, remove the bridge
between terminals X4.0 and X4.10 (see par. 8.8) and connect the
remote start/stop switch (to be provided by the customer).
In ON status, use the button with the following logic:
X4.0
X4.10
X4.0
X4.10
DRYER STATUS
ON
REMOTE OFF
!
Do not activate ONstatus (refrigeration compressor operat-
ing) more than 10 times in one hour.
Energy saving function
è
In ON mode, operating conditions permitting, the dryer reduces
energy consumption by temporarily switching off the refrigera-
tion compressor; the ENERGY SAVING LED (3) comes on (see
Control Panel).
Scheduled maintenance
Y
When the DISPLAY
[
alternatively shows the
Sr
warn-
ing code and dew point, contact authorized assistance personnel
for carrying out scheduled maintenance indicated in par. 6.3 and
for resetting the warning code (see par. 5.4 in List of alarm/warn-
ings).
Press
z
to cancel the warning for 24 hours.
Condensate drain
There are three operation modes:
a) INTEGRATED --- draining controlled by the level sensor;
b) TIMED --- draining at set intervals;
c) EXTERNAL --- if there is an external drain.
To change operation mode, use the parameter
d3
(see par. 5.3 in
List of parameters).
Y
Only set the EXTERNAL mode in absence of the solenoid
valve. Otherwise the relative coil could become damaged.