background image

The appliance must be isolated from the gas supply piping during any pressure 

testing of the gas supply piping system at test pressure equal to or less than 1/2 PSIG.

1

.  Connect gas line to the 3/8” elbow at the front of the furnace. (See Figure 1.) 

Some standards may require the use of a manual shut off valve in the gas line 

external to the furnace cabinet.

2

.  In order to maintain a check of gas supplied pressure to the furnace, 

Suburban advises the installer to provide the 1/8” NPT plug tap for test gauge 

connection immediately upstream of the gas supply connection to the furnace 

and that it be readily accessible.

3

.  After the furnace has been connected to the gas supply, all joints must be 

checked for leaks.

WARNING!

 

Never check for leaks with an open flame. Turn on the gas and apply soapy 

water to all joints to see if bubbles are formed.

CONNECTING ELECTRICAL SUPPLY

CAUTION: This furnace is designed for negative ground 12 volt D.C. system 

only. Do not attempt to alter the furnace for a positive ground system or 

connect the furnace directly to 115 volts A.C. Damage to furnace component 

parts will occur. Connect only to a protected circuit fused for not more than 

20 amps.

Be sure all wiring to the furnace is of heavy enough gauge to keep the voltage 

drop through it to a minimum and to provide enough power for start-up surge. No. 

12 gauge wire is recommended. If any of the original wire that is supplied with the 

appliance must be replaced, it must be replaced with type 105° C or its equivalent.

Power supply connections are to be on the right side of the furnace. The wires are 

color coded, red for positive (+) and yellow for negative (-). This polarity must be 

observed so the furnace motor will run the proper direction of rotation to insure 

correct air delivery. (See wiring diagram.)

If the furnace power supply is to be from a converter, we recommend that the 

converter system used to power the furnace be wired in parallel with the battery. 

This will serve two purposes:

1

.  Provide a constant voltage supply to the furnace.

2

.  Filter any A.C. spikes or volt surges.

CONNECTING DUCTS TO FURNACE

The following duct requirements must be followed in order to assure proper 

operation of the furnace:

A

.  The minimum open duct areas listed below must be maintained throughout 

entire duct system including through register:

MODEL

SIDE DUCTS

TOP 

DUCT

BOTTOM 

DUCT

Min. Open 

Duct Area

Min No. 

Ducts Used

Duct 

Size

Min. Open 

Duct Area

Min. Open 

Duct Area

SF-20FQ

25 SQ. IN.

2

4”

56 SQ. IN.

56 SQ. IN.

SF-25FQ

36 SQ. IN.

3

4”

56 SQ. IN.

56 SQ. IN.

SF-30FQ

36 SQ. IN.

3

4”

56 SQ. IN.

56 SQ. IN.

SF-35FQ

48 SQ. IN.

4

4”

56 SQ. IN.

56 SQ. IN.

SF-42FQ

48 SQ. IN.

4

4”

56 SQ. IN.

*72 SQ. IN.

*SF-42Q Bottom Duct requires use of Bottom Duct Kit, Part No. 520753

**SF-20/25/30Q has two 4” round ducts available off of cabinet front.

***SF-35/42Q has three 4” round ducts available off of cabinet front.This front is not to 

be used on SF-20/25/30Q

NOTE

: Ducts terminating in a dead air space (like holding tank compartments or 

cargo areas (Toy Boxes) with no means for return air recirculation should not be 

counted in the required duct area. Also ducts 2” in diameter or smaller should not 

be counted in the required duct area.

B. 

No outlet register is to be placed within 18” of the return air opening.  Any 

register installed at 18” should never be adjusted to blow the outlet air toward 

the return air opening.  If a register is installed on a wwall 90 degrees to the 

return air, it can be less than the 18”.

C

.  Make the duct connections at the furnace cabinet tight. Loose connections will 

result in overheating of the component parts on the furnace and a reduction of 

the heated air flow through the duct system.

D

.  Avoid making any sharp turns in the duct system. Sharp turns will increase 

the static pressure in the plenum area and could cause the furnace to cycle.

E

.  Avoid making a lot of turns in the duct system. The straighter the duct system, 

the better the performance of the furnace.

F

.  Maintain  a  minimum  of  1/4”  clearance  where  ducts  pass  through  any 

combustible construction, such as coach cabinetry. (See Figure 3.) 

NOTE

UL listed duct materials can be 0” clearance.

G

.  Do not install air boosters in the duct system. Such devices will cause the 

furnace to cycle on limit and to have erratic sail switch operation.

NOTE

: After installation of the furnace and duct system is completed, adjustments 

must  be  made  to  obtain  a  temperature  rise  within  the  range  specified  on  the 

Rating Plate.

INSTALLING THERMOSTAT

The thermostat used with this unit must have NO voltage output to return leg when 

there is not a call for heat or in the “OFF” setting. 

Locate the room thermostat approximately 4-1/2 feet above the floor on an inside 

bulkhead where it is not affected by heat from any source except room air. Connect 

thermostat wiring to the blue wire and blue-white striped wire (blue-white striped 

wire is power to the thermostat) on right side of furnace. (See wiring diagram.)  If 

your furnace is equipped with a thermostat that has an adjustable anticipator, the 

anticipator should be set at .7 amps. If you desire longer heating cycles, adjust 

the anticipator to a higher setting. If you desire shorter heating cycles, adjust the 

anticipator to a lower setting. Adjustments to the anticipator setting should be 

made in .5 amp increments.

PREVENTIVE MAINTENANCE

WARNING!

 

If the user of this appliance fails to maintain it in the condition in which it was 

shipped from the factory or if the appliance is not used solely for its intended purpose or if 

appliance is not maintained in accordance with the instructions in this manual, then the risk 

of a fire and/or the production of carbon monoxide exists which can cause personal injury, 

property damage or loss of life.

CAUTION: Label all wires before disconnecting for servicing. Proper polarity 

must be observed so the furnace motor will run with the proper direction of 

rotation to insure correct air delivery. (See wiring diagram).

CAUTION: Label all wires prior to disconnection when servicing controls. 

Wiring error can cause improper and dangerous furnace operation.

Always verify proper operation of furnace after servicing.

Your  furnace  should  be  inspected  by  a  qualified  service  agency  yearly  before 

turning the furnace on. Particular attention should be given to the following items:

1

.  Inspect furnace installation and vent termination to be sure furnace is 

properly secured in place (see Installation Instructions), that vent terminates 

to the atmosphere, and that vent tubes overlap properly (see Installing Vent 

Assembly.)

2

.   Inspect chamber and venting to assure that these components are physically 

sound without holes or excessive corrosion and that the installation and/

or re-installation is in accordance with Suburban’s installation instructions. 

(Reference installation manual supplied with furnace.)

WARNING!

 

It is imperative that the products of combustion be properly vented 

to atmosphere and that all combustion air supplied to burner be drawn from outside 

atmosphere.

3

.  Check the base on which furnace is mounted. Be sure it is physically sound, 

void of any sagging, deterioration, etc.

4

.  Inspect furnace, the venting, ducting and gas piping to furnace for obvious 

signs of deterioration. Correct any defects at once.

5

.  Inspect combustion chamber for restrictions in exhaust or intake. It is 

imperative  that  the  flow  of  intake  combustion  air  and  the  flow  of  exhaust 

gases being expelled to the outside atmosphere not be obstructed. Any soot 

or loose debris should be blown out using compressed air. (See Figure 6.)

6

.  Inspect all gaskets. If any gaskets show signs of leakage or deterioration, 

replace them. Safe operation of the furnace depends on all gaskets being 

tight.

7

.  Inspect return air inlet openings to the furnace. Remove any restrictions to 

assure adequate air flow.

You,  as  the  owner/user,  should  inspect  the  furnace  monthly  during  the 

heating season for presence of soot on vent. Operating the furnace under 

this  condition  could  lead  to  serious  property  damage,  personal  injury  or 

loss of life. If soot is observed on the vent, immediately shut the furnace 

down and contact a qualified service agency.

Listed below are several safety related items that you should follow during the 

heating season to assure continued safe operation of the furnace.

1

.  Inspect furnace venting. Venting must be free of obstructions, void of soot, 

and properly terminated to the atmosphere. (See Installing Vent Assembly.)

WARNING!

 

Do not install screens over the vent for any reason. Screens will become 

restricted and cause unsafe furnace operation. Accessories are being marketed for RV 

products which we do not recommend. For your safety, only factory authorized parts are to 

be used on your furnace.

2

.    Periodically  inspect  the  vent  for  obstructions  or  presence  of  soot.  Soot  is 

formed whenever combustion is incomplete. This is your visual warning that 

the furnace is operating in an unsafe manner. If soot is present, immediately 

shut furnace down and contact your dealer or a qualified service person.

3

.  Keep furnace clean. More frequent cleaning may be required due to excessive 

lint from carpeting, bedding material, etc. It is imperative that control 

compartments, burners and circulating air passageways of the appliance be 

kept clean.

3

Summary of Contents for SF-20FQ

Page 1: ...TO BE INSTALLED VERTICALLY YOU MUST USE KIT 520965 INSTALLATION INSTRUCTIONS ARE ENCLOSED IN KIT CAUTION If possible do not install the furnace to where the vent can be covered or obstructed when any...

Page 2: ...nting of furnace exhaust 5 After determining x dimension complete the furnace installation as follows A IF INSTALLED DIRECTLY AGAINST OUTER SKIN OR X DIMENSION IS 0 1 1 2 1 Vent Kit 520767 must be ord...

Page 3: ...e output to return leg when there is not a call for heat or in the OFF setting Locate the room thermostat approximately 4 1 2 feet above the floor on an inside bulkhead where it is not affected by hea...

Page 4: ...Turn the manual valve if so equipped or the valve at the outside LP tank to the OFF position Do not force 3 Set thermostat above room temperature to begin blower operation A slight delay will occur be...

Page 5: ...P AND EXHAUST TUBE INTAKE AIR WITH GASKET OUTSIDE SKIN PANEL Figure 1 SF 20FQ SF 25FQ SF 30FQ SF 35FQ SF 42FQ STANDARD VENT INSTALLATION X INTAKE 1 2 MINIMUM OVERLAP EXHAUST 1 1 4 MINIMUM OVERLAP 2 3...

Page 6: ...GREEN ALL WIRES ARE 18 AWG UNLESS OTHERWISE SPECIFIED IF ANY OF THE ORIGINAL WIRES AS SUPPLIED WITH THE APPLIANCE MUST BE REPLACED IT MUST BE REPLACED WITH WIRING MATERIAL HAVING A TEMPERATURE RATING...

Page 7: ...M THE CABINET AND THE MANIFOLD BLOWER ASSEMBLY AND CONTROLS REMO VED LEAVING THE CHAMBER ONLY AS SHOWN USING COMPRESSED AIR B LOW THROUGH THE CHAMBER AS SHOWN BY ARROWS TO REMOVE SOOT OR LOOS E DEBRIS...

Page 8: ...TIES INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY ARE HEREBY LIMITED IN DURATION TO THE PERIOD FOR WHICH EACH LIMITED WARRANTY IS GIVEN SOME STATES DO NOT ALLOW LIMITATIONS ON HOW LONG AN IMPLIED W...

Page 9: ...iqu es pour la garantie de deux ann es L EXCEPTION que Suburban ne remboursera aucun frais de main d oeuvre LIMITATION DES GARANTIES LA P RIODE DE VALIDIT DES GARANTIES IMPLICITES CECI INCLUANT LES GA...

Page 10: ...alement le ventilateur et les organes de commande il ne doit rester que la chambre de combustion comme on le voit sur l illustration Injecter de l air comprim dans la chambre selon les indications des...

Page 11: ...DE COURSE N C CONTACTEUR DE Y Y Y BR BK MOTEUR L INTERRUPTEUR EN MARCHE ARRET N C BL BK BK Y BR R Y O R BL WH POUVOIR DE THERMOSTAT R 12 V D C Y 12 V D C BL THERMOSTAT FR340571 12 VOLTS D C R CLAPET...

Page 12: ...G N REUSEMENT AUTOUR DU P RIM TRE DU COUVERCLE DU SYSTEME D ADMISSION ET DE D CHARGE D AIR ET SUR LA LIGNE DE CENTRE COMME INDIQU LE CALFATAGE DE LA LIGNE DE CENTRE EST ESSENTIEL D TAIL A TUBE D ADMIS...

Page 13: ...nt la chambre la caisse 3 R installer le panneau avant de la caisse 4 Connecter la source de gaz 5 Inspecter les connexions de la canalisation de gaz Rechercher les fuites avec une solution savonneuse...

Page 14: ...e sur la plaque signal tique INSTALLATION DU THERMOSTAT Le thermostat utilis avec cet appareil ne doit avoir AUCUNE tension de sortie dans la tige de retour lorsqu il n y a aucun appel de chaleur ou...

Page 15: ...1 4 pouces de diam tre dans le panneau externe du v hicule come indiqu dans la Figure 1 4 Mettez l appareil en place en vous assurant que l arri re de l appareil soit aussi pr s que possible de la par...

Page 16: ...our la combustion soit pr lev dans l atmosph re ext rieure Voir Installation du syst me d admission d air et vacuation des gaz de combustion REMARQUE Lors de l installation de l appareil ne pas orient...

Reviews: