background image

13

14

Sr. 

No.

Parameter setting method

Description of parameters and functions.

Parameter

Sr. 

No.

Parameter setting method

Description of parameters and functions.

Parameter

C-OL
Parameter

12

Function : Over load limit for compressor 
current.

To change the C-OL parameter, 
press the set key.

Use UP/DOWN keys to set desired value.

Example :

 If C-OL= 10 A and compressor 

current is greater than 10 A then and exist 
till  C2  current  sensing  delay  then  C-OL 
fault  exists  and  flash  on  display. 
Compressor will be tripped on this fault.

NOTE  : According  to  the  compressor 
current, set Overload value.

(C-UL

+1.0) A

30.0A

10.0A

Range

Min

Max

Fact. Set 

Use UP/DOWN keys to set desired value.

Example :

 If C2 = 5 sec then, any current 

fault  will  be  valid  only  when  it  exists  for 
more than 5 sec.

To change the C2 parameter, 
press the set key.

C2
Parameter

13

Function  : Current sensing delay.

5 Sec

60 Sec

5 Sec

Range

Min

Max

Fact. Set 

Use UP/DOWN keys to set desired value.

Example : 

If this parameter is set to

ENB : HP sensing is enabled.
DIS  : HP sensing is disabled

Setting this parameter to disable will 
ignore HP fault for compressor. If this 
parameter is set to Enable then controller 
will detect HP trip. 

To change the D0 parameter, 
press the set key.

D0
Parameter

14

Function : To enable or Disable HP 
sensing. 

DIS 

ENB

ENB

Range

Min

Max

Fact. Set 

Use UP/DOWN keys to set desired 
value.

Example:

  

If this parameter is set to 
ENB : LP sensing is enabled.
DIS  : LP sensing is disabled.

To change D1
parameter, press the set key.

DIS 

ENB

D1 
Parameter

15

ENB

Function : To enable or disable LP 
sensing.

Range

Min

Max

Fact. Set 

D2
Parameter

16

To change D2 parameter, 
press the set key.

0V

230V

Function : Fault sensing logic.

0V

Use UP/DOWN keys to set desired 
value.

0V  :  0V at HP/LP/AUX input will be 

sensed as fault and trip the 
compressor.

230V :  230V at HP/LP/AUX input will be 

    sensed as fault and trip the 
    compressor.

Range

Min

Max

Fact. Set 

Setting  this  parameter  to  disable  will 
ignore  LP  fault  for  compressor.  If  this 
parameter is set to Enable then controller will 
detect LP trip. 

To change D3 parameter,
press the set key.

0 Sec

17

Min

Min

Use UP/DOWN keys to set desired value.

Example :

 If this parameter is set to 30 

sec,  then  LP  fault  will  be  sensed  only 
when it present continuously for 30 Secs.

180 Sec

30 Sec

D3
Parameter

Function : To set LP sensing delay.

Range

Max

Fact. Set 

Range

Max

Fact. Set 

18.0A

CRC-2020

CRC-2020

Summary of Contents for CRC-2020

Page 1: ...AMP CRC 2020...

Page 2: ...ssor current C OL 13 Current sensing delay C2 13 To enable or Disable HP sensing D0 13 To enable or disable LP sensing D1 14 Fault sensing logic D2 14 To set LPsensing delay To set reset mode for HPfa...

Page 3: ...t up the instrument for each specific function The CRC 2020 controller can be used for several applications with a measuring range from O O 50 0 C to 50 0 C Computer Connectivity over RS485 and Remote...

Page 4: ...croll in Program mode Used to enter into the program mode Used to switch OFF ON the light Used to enter into the Amp mode where compressor current can be viewed AMP High temperature alarm for Room mea...

Page 5: ...that the set point has been stored in memory 01 To change Set Point parameter press the set key P3 0 5 C P2 0 5 C 0 0 C Range Min Max Fact Set To set other parameter Press hold PRG key for 2 seconds D...

Page 6: ...the set point 0 is set at 10 0 C and differential is set at 0 2 0 C then when the system reaches 0 10 0 C the comp relay will cutout Since 0 the differential is 2 0 C the comp Relay 0 will cutin at 1...

Page 7: ...ill take place once Example If P9 parameter is 30 mins then at power after 30 mins defrosting will take place once BUZ Parameter 09 Function To enable disable buzzer To change the BUZ Parameter parame...

Page 8: ...ault for compressor If this parameter is set to Enable then controller will detect HP trip To change the D0 parameter press the set key D0 Parameter 14 Function To enable or Disable HP sensing DIS ENB...

Page 9: ...emperature will be dispalyed DEFR At Defrosting Defrost ON will scroll 24 Function To set Display at defrosting To change E7 parameter press the SET key TEMP DEFR TEMP Range Min Max Fact Set Range Min...

Page 10: ...ed to set the Unit ID of the device 29 Function To set Unit ID To change Unit ID parameter press the SET key 1 240 Range Min Max Fact Set Range Min Max Fact Set NO YES NO CCRH 28 Function Clear Compre...

Page 11: ...normal mode and displays the Room Temperature and all settings are recorded 34 Function To exit programming To exit programming parameter press the SET key 20 CRC 2020 Technical Data Housing Plastic...

Page 12: ...To set Reference Voltage 23 23 DESCRIPTION PARAMETER Pg No To set program mode 23 To set Undervoltage Limits 25 To set Un Balance Value To set Time Delay 25 To set Calibration of Voltage To set Calib...

Page 13: ...ce value To change the unb parameter press the set key 10V 120V 60V Range Min Max Fact Set Use UP DOWN keys to set desired value If the a c voltages goes below this limit will trip respective a c on u...

Page 14: ...t desired value There are two type of display output Line to Line Voltage L L and Line to Neutral L n Depending on this parameter REF parameter also changes 26 Sr No Parameter setting method Descripti...

Page 15: ...1 2 RELAY NC C NO 3 7 8 9 R 15 17 19 18 21 Y B N Main Functions Voltage Monitoring Phase Sequence Monitoring Phase Loss and Phase Unbalance detection Uv and Ov Detection Settable Uv and Ov Parameter...

Page 16: ...29...

Page 17: ...mages No part of this manual may be reproduced or transmitted in any form or by any means without the prior written permission of the company Notice Disclaimer Warranty This manual its contents remain...

Page 18: ...Globe Valves Hand Valves Flow Switches Solenoid Valves OUR OTHER PRODUCTS Cold Room Controller Chiller Controller Two Compressors Controller Heating Controller Humidity Controller Pressure Controller...

Reviews: