Parameter setting method

Description of parameters and functions.

Parameter

01

P2 
Parameter

Function : To set allowable high 
temperature limit. 

To change P2 parameter, 
press the set key.

Use UP/DOWN key to set desired value. 
Once set at a particular value, this will not 
allow  the  set  point  to  go  above  this
value and below P3 setting.

Example :

 Setting this parameter

0

at 50.0 C  will not allow  the set point to go 

0

above  50.0 C  also  if  the    temperature 

0

reaches 50.0 C, the display will show  HT 
(High  Temperature).  The  alarm  will  be 
ON.  But  at  power  on  till  the AL  delay  is 
over controller will not generate HT Alarm. 

SP+0.5ºC

50.0ºC

50.0ºC

Range

Min

Max

Fact. Set 

(Message on Display)

09

Sr. 

No.

Parameter setting method

Description of parameters and functions.

Parameter

02

P3
Parameter

Function : To set allowable low 
temperature limit.

Use UP/DOWN key to set desired value. 
Once set at a particular value, this will not 
allow the set point to go below this value 
and above P2 setting.

Example : 

 Setting this parameter at 

0

-50.0 C will not allow   the set point to go 

0

below  -50.0 C  also  if  the  temperature 

0

reaches -50.0 C, the display will show  LT 
(Low Temperature). The alarm will be ON. 

To change 

parameter, 

press the set key.

P3 

-50.0ºC

SP-0.5ºC

-50.0ºC

Range

Min

Max

Fact. Set 

(Message on Display)

Use UP/DOWN keys to set desired value.

Example(Cooling Mode) :

  If the set point 

0

is set at 10.0 C and differential is   set at 

0

2.0 C,  then  when  the    system  reaches 

0

10.0 C, the   comp. relay will cutout. Since 

0

the  differential  is  2.0 C,  the  comp.  Relay 

0

will cutin at 12.0 C

0

0

(10.0 C + 2.0 C).  

03

P4
Parameter

Function : To set the differential for 
compressor restart. 

To change 

P4 

press the set key.

parameter, 

0.5ºC

20.0ºC

2.0ºC

Range

Min

Max

Fact. Set 

P5
Parameter

Use UP/DOWN keys to set desired value. 
In time it may be possible that the display 
may be offset by a degree or so.
To  compensate  for  this  error,  you  may 
need  to  add  or  minus  the  degrees 
required  to  achieve  the  correct 
temperature. 

Example  :

  The  temperature  on  the 

O

display  is  28.0 C,  whereas  the  actual 

O

temperature is 30.0 C. You will need to set 

O

this parameter to 2.0 C, which means that 
once out of the programming parameter, 
the  display  will  show  the  temperature 

O

O

O

30.0 C (28.0 C + 2.0 C).

To change P5 
press the set key.

parameter, 

04

Function : To set  probe calibration.

-10.0ºC

10.0ºC

0.0ºC

Range

Min

Max

Fact. Set 

HT

LT

Use UP/DOWN keys to set desired value. 
This parameter is used to protect the fan 
from  restarting  in  a  short  period  of  time 
and can be set between 0 to 20 minutes.

Example :

  If this parameter is set at 3 

minutes, the compressor will cut off at 
the set temperature, but will not restart 
for a minimum of 3 minutes, even if the 
differential is achieved earlier. This 

P6
Parameter

To change P6 
press the set key.

parameter, 

05

Function : To set time delay between 
relay restart time.

1 Min

20 Min

3 Min

Range

Min

Max

Fact. Set 

CRC-2020

CRC-2020

Summary of Contents for CRC-2020

Page 1: ...AMP CRC 2020...

Page 2: ...ssor current C OL 13 Current sensing delay C2 13 To enable or Disable HP sensing D0 13 To enable or disable LP sensing D1 14 Fault sensing logic D2 14 To set LPsensing delay To set reset mode for HPfa...

Page 3: ...t up the instrument for each specific function The CRC 2020 controller can be used for several applications with a measuring range from O O 50 0 C to 50 0 C Computer Connectivity over RS485 and Remote...

Page 4: ...croll in Program mode Used to enter into the program mode Used to switch OFF ON the light Used to enter into the Amp mode where compressor current can be viewed AMP High temperature alarm for Room mea...

Page 5: ...that the set point has been stored in memory 01 To change Set Point parameter press the set key P3 0 5 C P2 0 5 C 0 0 C Range Min Max Fact Set To set other parameter Press hold PRG key for 2 seconds D...

Page 6: ...the set point 0 is set at 10 0 C and differential is set at 0 2 0 C then when the system reaches 0 10 0 C the comp relay will cutout Since 0 the differential is 2 0 C the comp Relay 0 will cutin at 1...

Page 7: ...ill take place once Example If P9 parameter is 30 mins then at power after 30 mins defrosting will take place once BUZ Parameter 09 Function To enable disable buzzer To change the BUZ Parameter parame...

Page 8: ...ault for compressor If this parameter is set to Enable then controller will detect HP trip To change the D0 parameter press the set key D0 Parameter 14 Function To enable or Disable HP sensing DIS ENB...

Page 9: ...emperature will be dispalyed DEFR At Defrosting Defrost ON will scroll 24 Function To set Display at defrosting To change E7 parameter press the SET key TEMP DEFR TEMP Range Min Max Fact Set Range Min...

Page 10: ...ed to set the Unit ID of the device 29 Function To set Unit ID To change Unit ID parameter press the SET key 1 240 Range Min Max Fact Set Range Min Max Fact Set NO YES NO CCRH 28 Function Clear Compre...

Page 11: ...normal mode and displays the Room Temperature and all settings are recorded 34 Function To exit programming To exit programming parameter press the SET key 20 CRC 2020 Technical Data Housing Plastic...

Page 12: ...To set Reference Voltage 23 23 DESCRIPTION PARAMETER Pg No To set program mode 23 To set Undervoltage Limits 25 To set Un Balance Value To set Time Delay 25 To set Calibration of Voltage To set Calib...

Page 13: ...ce value To change the unb parameter press the set key 10V 120V 60V Range Min Max Fact Set Use UP DOWN keys to set desired value If the a c voltages goes below this limit will trip respective a c on u...

Page 14: ...t desired value There are two type of display output Line to Line Voltage L L and Line to Neutral L n Depending on this parameter REF parameter also changes 26 Sr No Parameter setting method Descripti...

Page 15: ...1 2 RELAY NC C NO 3 7 8 9 R 15 17 19 18 21 Y B N Main Functions Voltage Monitoring Phase Sequence Monitoring Phase Loss and Phase Unbalance detection Uv and Ov Detection Settable Uv and Ov Parameter...

Page 16: ...29...

Page 17: ...mages No part of this manual may be reproduced or transmitted in any form or by any means without the prior written permission of the company Notice Disclaimer Warranty This manual its contents remain...

Page 18: ...Globe Valves Hand Valves Flow Switches Solenoid Valves OUR OTHER PRODUCTS Cold Room Controller Chiller Controller Two Compressors Controller Heating Controller Humidity Controller Pressure Controller...

Reviews: