Sub-Zero CRC-2020 User Manual Download Page 5

08

07

Min: MINIMUM   Max : MAXIMUM
Fact. Set : FACTORY SETTING(DEFAULT)

Sr. 

No.

Parameter setting method

Description of parameters and functions.

Parameter

To set other parameter

Press & hold SET key for 
2 seconds 

Display will show ‘SET’ and scroll the 
description of the parameter.

To go to other parameters, use UP / 
DOWN keys.

SP

To set the cut-out point of the controller.

Display will change to set value.
The set point value can now be changed by 
using  the  UP/DOWN  key.  After  desired 
value, press the SET key & you will see “--” 
which confirms that the set point has been 
stored in memory. 

01

To change Set Point parameter, 
press the set key.

P3+0.5ºC P2-0.5ºC

0.0ºC

Range

Min

Max

Fact. Set 

To set other parameter

Press & hold PRG key for 
2 seconds 

Display will show ‘P2’ and scroll the 
description of the parameter.
To go to other parameters, use UP / 
DOWN keys.

PRG

LED Indication 

Messages

Mode

Discription

Comp. Relay On.
Comp. Relay Off.
Comp. Relay Timedelay.

Defrost On.
Defrost Off.
Defrost in Timedelay.

Alarm Relay On.
Alarm Relay Off.

Power Off.
Power On.

Light Relay On.
Light Relay Off.

R-phase present.
R-phase absent.

R

Y-phase present.
Y-phase absent.

Y

B-phase present.
B-phase absent.

B

On
Off
Flashing

On
Off
Flashing

On
Off

Off
On

On
Off

On
Off

On
Off

On
Off

CRC-2020

CRC-2020

Summary of Contents for CRC-2020

Page 1: ...AMP CRC 2020...

Page 2: ...ssor current C OL 13 Current sensing delay C2 13 To enable or Disable HP sensing D0 13 To enable or disable LP sensing D1 14 Fault sensing logic D2 14 To set LPsensing delay To set reset mode for HPfa...

Page 3: ...t up the instrument for each specific function The CRC 2020 controller can be used for several applications with a measuring range from O O 50 0 C to 50 0 C Computer Connectivity over RS485 and Remote...

Page 4: ...croll in Program mode Used to enter into the program mode Used to switch OFF ON the light Used to enter into the Amp mode where compressor current can be viewed AMP High temperature alarm for Room mea...

Page 5: ...that the set point has been stored in memory 01 To change Set Point parameter press the set key P3 0 5 C P2 0 5 C 0 0 C Range Min Max Fact Set To set other parameter Press hold PRG key for 2 seconds D...

Page 6: ...the set point 0 is set at 10 0 C and differential is set at 0 2 0 C then when the system reaches 0 10 0 C the comp relay will cutout Since 0 the differential is 2 0 C the comp Relay 0 will cutin at 1...

Page 7: ...ill take place once Example If P9 parameter is 30 mins then at power after 30 mins defrosting will take place once BUZ Parameter 09 Function To enable disable buzzer To change the BUZ Parameter parame...

Page 8: ...ault for compressor If this parameter is set to Enable then controller will detect HP trip To change the D0 parameter press the set key D0 Parameter 14 Function To enable or Disable HP sensing DIS ENB...

Page 9: ...emperature will be dispalyed DEFR At Defrosting Defrost ON will scroll 24 Function To set Display at defrosting To change E7 parameter press the SET key TEMP DEFR TEMP Range Min Max Fact Set Range Min...

Page 10: ...ed to set the Unit ID of the device 29 Function To set Unit ID To change Unit ID parameter press the SET key 1 240 Range Min Max Fact Set Range Min Max Fact Set NO YES NO CCRH 28 Function Clear Compre...

Page 11: ...normal mode and displays the Room Temperature and all settings are recorded 34 Function To exit programming To exit programming parameter press the SET key 20 CRC 2020 Technical Data Housing Plastic...

Page 12: ...To set Reference Voltage 23 23 DESCRIPTION PARAMETER Pg No To set program mode 23 To set Undervoltage Limits 25 To set Un Balance Value To set Time Delay 25 To set Calibration of Voltage To set Calib...

Page 13: ...ce value To change the unb parameter press the set key 10V 120V 60V Range Min Max Fact Set Use UP DOWN keys to set desired value If the a c voltages goes below this limit will trip respective a c on u...

Page 14: ...t desired value There are two type of display output Line to Line Voltage L L and Line to Neutral L n Depending on this parameter REF parameter also changes 26 Sr No Parameter setting method Descripti...

Page 15: ...1 2 RELAY NC C NO 3 7 8 9 R 15 17 19 18 21 Y B N Main Functions Voltage Monitoring Phase Sequence Monitoring Phase Loss and Phase Unbalance detection Uv and Ov Detection Settable Uv and Ov Parameter...

Page 16: ...29...

Page 17: ...mages No part of this manual may be reproduced or transmitted in any form or by any means without the prior written permission of the company Notice Disclaimer Warranty This manual its contents remain...

Page 18: ...Globe Valves Hand Valves Flow Switches Solenoid Valves OUR OTHER PRODUCTS Cold Room Controller Chiller Controller Two Compressors Controller Heating Controller Humidity Controller Pressure Controller...

Reviews: