Stûv 30-up - installation [en] - 0209
SN 68 719 > ...
It will probably be necessary to
shorten the convection column. Its
standard length is 1,428 mm.
Please note: The height of the column
after shortening will still be at least
828 mm.
Determining the length to cut
Measure the height H.
In configurations 1, 2 and 4 (see
page 12), H = the height under the
ceiling. With a wall connection -
configurations 5 and 6 - [figure 1],
measure from the highest part of the
connection chamber to the floor.
With a union extending from the
ceiling (configuration 2) and therefore
the finished ring option, measure the
height from the lower face of the ring
[figure 2].
Before cutting, the height H of the
standard parts is 290 cm. Deduct
the height measured from this figure
to give how much to cut the parts
by (the front and back parts of the
convection column and possibly the
insulating panel)
Example: with a measured height of
265 cm, cut each part by
290 – 265 = 25 cm.
Cutting
Separate the two pieces of the
convection column [photo 3]. The
side illustrated in photo 3 must remain
intact; the upper part of the column
remains visible. Cut the other side
by a maximum of 60 cm (otherwise
the safety of the installation may be
compromised). The cut will be hidden
under the plate of the stove.
The 2 parts – front and back – of the
convection column are not the same
height. This is normal.
Positioning
Position the front part of the column,
pulling open the sides when inserting
[photo 4]. It is placed onto 4 screws
with cylindrical heads [photo 5-a]. The
folds at the back rest on them [b].
Inserting the convection column