STULZ Ultra-Series Humidifier Controller
(August, 2013)
47
5.7.9.1 Set
Passwords
5.7.9.2 Factory Save Access
5.7.9.3 Factory
Save
After the factory settings have been completed, they can
be saved into permanent memory. It also should be saved
into the customer’s memory. This allows the restoration to
the factory settings, if the customer inadvertently sets up
situations that cause erratic behavior. By returning to this
screen the STULZ Product Support technician can restore
the settings back to the factory settings.
5.7.9.3.1 Initialization
This screen is used to set the entire permanent memory
values back to their default values. This must be done any
time new software is downloaded. Use the Enter key to
position the cursor at the “No” text and then press either
the Up or Down key to start the initialization process. The
area labeled status will show the progress.
When it is done, it will go back to the Basic System
Configuration screen.
5.8 Factory Default Set Points
Table 1- Default Set Points
Parameter
Set Point
Remote Enable
Yes
Customer Alarm 1 Enable
No
Airflow Enable
No
BMS keep alive Override
No
Smoke Alarm Enable
No
High humidity Switch Enable
No
Customer Alarm 2 Enable
No
Humidifier Temperature Enable
No
Customer Alarm 3 Enable
No
Group Select
No
Cabinet Fan Enable
Yes
Custom Alarm 1 Output Enable
No
Custom Alarm 2 Output Enable
No
Custom Alarm 3 Output Enable
No
Custom Alarm 4 Output Enable
No
Log Remote Shutdown
No
Bank Enable
No
High Airflow Alarm Enable
No
Low Airflow Alarm Enable
No
High limit humidity alarm Enable
No
Control Temperature Enable
No
Control Humidity Enable
Yes
Conductivity Enable
Yes
Limit Temperature Enable
No
Limit Humidity Enable
No
Airspeed Enable
No
Low Limit Humidity Alarm Enable
No
NTC2 Temperature Sensor Enable
No
NTC3 Temperature Sensor Enable
No
NTC4 Temperature Sensor Enable
No
Control Temperature X Low Scale
0
Control Temperature X High Scale
50.0
Control Humidity X Low Scale
0
Control Humidity X High Scale
100.0
Limit Temperature X Low Scale
0
Limit Temperature X High Scale
50.0
Limit Humidity X Low Scale
0
Limit Humidity X High Scale
100.0
Remote On/OFF Invert
Yes
Customer Alarm 1 Invert
Yes
Airflow Switch Invert
Yes
Water Detector Invert
Yes
Smoke Alarm Invert
Yes
High Humidistat Invert
Yes
Customer Alarm 2 Invert
Yes
Freeze Alarm Invert
Yes
Control:
1
Service:
2
Factory:
xxxxx
Config:
xxxxx
Set Passwords
Password Config
FACT SAVE
Initialize Variables
software details that are
MUST SAVE BOTH FACTORY
AND CUSTOMER VALUES
Save Factory
No
Save Customer No
Restore Factory No
Factory Save
DEFAULT INITIALIZATION
Erase user settings
and install global
default values: No
status
Initialization