STULZ Ultra-Series Humidifier Controller
(August, 2013)
55
Modbus
TCP/IP
BMS
Address
Modbus
Address
BACnet
Address
Description Default
Read/
Write
5017
16
40145
1016
Packed bits for BMS – Humidifier 12 Alarms
R
5018
17
40146
1017
Packed bits for BMS – Humidifier 13 Alarms
R
5019
18
40147
1018
Packed bits for BMS – Humidifier 14 Alarms
R
5020
19
40148
1019
Packed bits for BMS – Humidifier 15 Alarms
R
5021
20
40149
1020
Packed bits for BMS – Humidifier 16 Alarms
R
5022
21 40150 1021
Packed bits for BMS – Raw digital inputs
R
5023
22 40151 1022
Packed bits for BMS – Digital inputs 2
R
5024
23 40152 1023
Packed bits for BMS – Digital outputs
R
5025
24 40153 1024
Packed bits for BMS – Humidifier 1 Digital outputs
R
5026
25 40154 1025
Packed bits for BMS – Humidifier 2 Digital outputs
R
5027
26 40155 1026
Packed bits for BMS – Humidifier 3 Digital outputs
R
5028
27 40156 1027
Packed bits for BMS – Humidifier 4 Digital outputs
R
5029
28 40157 1028
Packed bits for BMS – Humidifier 5 Digital outputs
R
5030
29 40158 1029
Packed bits for BMS – Humidifier 6 Digital outputs
R
5031
30 40159 1030
Packed bits for BMS – Humidifier 7 Digital outputs
R
5032
31 40160 1031
Packed bits for BMS – Humidifier 8 Digital outputs
R
5033
32 40161 1032
Packed bits for BMS – Humidifier 9 Digital outputs
R
5034
33 40162 1033
Packed bits for BMS – Humidifier 10 Digital outputs
R
5035
34 40163 1034
Packed bits for BMS – Humidifier 11 Digital outputs
R
5036
35 40164 1035
Packed bits for BMS – Humidifier 12 Digital outputs
R
5037
36 40165 1036
Packed bits for BMS – Humidifier 13 Digital outputs
R
5038
37 40166 1037
Packed bits for BMS – Humidifier 14 Digital outputs
R
5039
38 40167 1038
Packed bits for BMS – Humidifier 15 Digital outputs
R
5040
39 40168 1039
Packed bits for BMS – Humidifier 16 Digital outputs
R
5041
40 40169 1040
Humidifier communications protocol level
R
5042
41 40170 1041
Number of hours left until drain occurs
R/W
5043 42 40171 1042
Not
used
5044
43
40172
1043
Percentage restriction on Group A output (0-100)
R/W
5045
44
40173
1044
Percentage restriction on Group B output (0-100)
R/W
5048
47
40048
47
Limit Mode 0=disabled;1=humidity;2=dewpoint
0
R/W
5101
100 40229 1100
Type of humidifier system (1 – DRH, 2 = DAH)
0
R
5102 101 40230 1101
Control method (0 = humidity, 1 = dew point, 2 =
proportional)
1 R
5103
102 40231 1102
Regulation mode – see section 5.7.1
2
R
5104
103 40232 1103
BMS keep alive (toggle between 1 & 2 every 10 mins.)
0
R/W
5124
123 40252 1123
Current day
1
R/W
5125
124 40253 1124
Current month
1
R/W
5126
125 40254 1125
Current year
0
R/W
5127
126 40255 1126
Current hour
0
R/W
5128
127 40256 1127
Current minute
0
R/W
10.3 Boolean Values for HTTP, SNMP / Modbus Coils / Binary Values for BACnet
Modbus
TCP/IP
BMS
Address
Modbus
Address
BACnet
Address Description Default
Read/
Write
002
1
002
1
Global alarm output
R
003
2
003
2
System on status
R
004
3
004
3
Airflow has been proven
R
005
4
005
4
Call for humidification
R
006
5
006
5
Lead Group (0 = Group A, 1 = Group B)
R/W
007
6
007
6
Customer alarm input 1
R/W
008 7 008 7
Condensate
Pan
R
009 8 009 8
Airflow
Switch
R
010 9 010 9
Water
Detector
R
011 10 011 10
High
Limit
Stat
R
012 11 012 11
Smoke
R