STULZ Ultra-Series Humidifier Controller
28
(August,
2013)
Conductivity Alarm
Conduct. Enable:No
Trip point: 20.0uS
Pre-Alarm Enable:No
Trip point: 5.0uS
Offset: 1.0°F
Alarm Delay: 90 sec
Airflow Alarm
High alarm Enable: No
Trip point: 1200.0 fpm
Low alarm Enable: No
Trip point: 600.0 fpm
Offset: 20.0 fpm
Alarm Set
CLOCK
Version
Limit Humidity
High alarm Enable:No
Trip point: 80.0%RH
Low alarm Enable:No
Trip point: 40.0%RH
Offset: 1.0°
Limit TemperatureHigh
alarm Enable:No
Trip point: 80.0°F
Low alarm Enable:No
Trip point: 40.0°F
Offset: 1.0°F
5.4.2.2 Control Humidity Alarms
If the control humidity sensor is enabled, high and low
alarms may be enabled and set to specific trip points. The
offset behaves in the same manner as described in section
5.4.2.1. It applies to both the high and low alarms.
5.4.2.3 Limit Temperature Alarms
If the limit temperature sensor is enabled, high and low
alarms may be enabled and set to specific trip points. The
offset behaves in the same manner as described in section
5.4.2.1. It applies to both the high and low alarms.
5.4.2.4 Limit Humidity Alarms
If the control humidity sensor is enabled, high and low
alarms may be enabled and set to specific trip points. The
offset behaves in the same manner as described in section
5.4.2.1. It applies to both the high and low alarms.
5.4.2.5 Conductivity
Alarms
If the conductivity sensor is enabled, a conductivity alarm
can be enabled and the trip point in MicroSiemens can be
adjusted. A Pre-conductivity alarm can be enabled and the
trip point in MicroSiemens can be adjusted.
The offset
behaves in the same manner as described in section
5.4.2.1. It applies to both the high and low alarms.
5.4.2.6 Airflow
Alarm
If the airflow sensor is enabled, high and low alarms may
be enabled and set to specific trip points. The offset
behaves in the same manner as described in section
5.4.2.1. It applies to both the high and low alarms.
Clock
Screen
5.4.3
Enter the Clock menu to change trip points for common
alarms on analog inputs.
Control
Control Humidity
High alarm Enable:No
Trip point: 80.0%RH
Low alarm Enable:No
Trip point: 30.0%RH
Offset: 1.0%RH