Failure to comply with these requirements, in addition to affecting proper unit
operation, invalidates warranty coverage.
adhesive gasket
WARNING!
Do not obstruct circulation by air being sucked into or expelled from the air
conditioner.
3
The cooling unit must be installed as high as possible;
4
If installed on a door, make sure the hinges can withstand the weight of the unit;
5
make sure the electric cable is not torn or damaged when the door is closed;
6
If the depth of the cooling unit prevents the door from being completely opened, arrange
a stopper for such a door.
7
Prior to servicing the cabinet, disconnect power supply to the same.
Prior to drilling holes or making cuts on the cabinet, make sure that holes, screws,
cables, etc. do not interfere with the equipment which has already been installed. Make
cuts on the cabinet panels by following the relevant template.
8
Once the anchoring holes have been drilled in the cabinet wall, mount the eyebolts to
handle the unit. the necessary cut-outs
corresponding to the unit size can be seen on
the following pages.
9
Glue the adhesive gasket around the edges of
the holes drilled on the cabinet;
10 Position the cooling unit at the cabinet and
secure it with the appropriate screws.
NOTE:
Mini-Air units are already provided with threaded
inserts, in correspondance with the fixing holes at the
cut-out.
Therefore the fixing holes at the cabinet wall must not
be provided with threaded inserts.
NOTE:
Mini-Air units are provided with a 3m power supply
cable. Therefore leave a minimum distance of 200 mm
from the top of the unit to the shelter ceiling during
installation.
threaded inserts
threaded inserts