E/1203/30A/19
7. Installation
1 Unpack the unit taking care not to damage its exposed parts. Before discarding it,
check the packaging for any parts or documents. Check that the supply voltage is as
designated.
2 Check that:
- there is space enough for an easy application and installation, both inside and
outside the cabinet;
- the cabinet is at least of the IP54 type;
- the cabinet is clean on the inside;
- the cabinet is not in the proximity of heat sources or warm air flows;
- the inside of the cabinet allows a proper air circulation, preventing any recirculation.
It is important to prevent hot air expelled by the condenser fan from being even partially
sucked back in. This would cause continuous stoppages, commanded by the pressure
switches, reducing efficiency and increasing electricity consumption. Improper operation
of this type can quickly cause irreparable harm to the compressor.
- units have to be fixed at the cabinet wall or at the cabinet door, which can support their
weight
6. Precautions when handling the Unit
To move this unit, when it is still packaged, use
a fork lift or a system using cables or chains.
When the packing is removed, use two M6
eyebolts, attaching them to the upper part of the
cooling unit, where appropriate holes have
already been arranged.
Summary of Contents for CVC 07 001yy
Page 2: ...E 1203 30A 2...