6. Installation
6.1 Positioning
Check that the installation site is appropriated for the unit weight, which you can read in the technical data.
The A/C unit is designed for the inside installation on a level base. The solid base frame contributes significantly to
an even weight distribution. When selecting the installation site take into account the necessary clearances for the
maintenance and the air flow.
Children, unauthorized persons and animals may not have access to the installation site of the A/C unit.
Vibrations emanate from the A/C unit due to compressor operation. To avoid such vibrations, install the unit on a
vibration absorbing base, as it is realized in case of a positioning on a raised floor socket e.g. by Mafund strips.
Do not operate the A/C unit in office rooms or other rooms sensitive to noise.
Maintenance
clearance
Air intake area
The unit may not be operated in an explosive atmosphere!
Before the positioning prepare the fan unit for the electrical wiring by unscrewing the fan protection grilles and by
removing the cable feedthrough plates.
The two cable feedthrough plates are located in the frame of the fan unit and
secured by two Torx screws that are screwed in from below.
2 screws
cable feedthrough plate with
6 openings
Bottom view
cable feedthrough plate
top view
The maintenance clearance of 1 m must also be maintained
in front of the fan unit in the raised floor.