ATI SP 80, 120, 220, 300, 400 – INSTALLATION INSTRUCTIONS
Sept - 01
2.4 INSTALLATION OF FLUE HOOD
The top cover of the water heater has four holes for
the fixing of flue hood, which allow four position of it,
one at 90° from each other. When an intermediate
position is necessary proceed as follows :
ATI SP 80 & 120
Position the flue hood on the water heater with the flue
and air intake in the desired direction. Drill the top
cover of the heater with a Ø 4mm drill, through the four
fixing brackets of the flue hood.
ILLUSTRATION 13A
Tighten the screws supplied for fixing the flue hood by
a few turns. Insert the seal between the flue hood and
the casing, exerting light pressure on it if necessary.
Tighten the screws with moderate force.
ATI SP 220, 300 & 400
Position the flue hood on the water heater, as in
illustration 14b, with the flue and air intake in the
desired direction.Drill the top cover of the heater with a
Æ
4mm drill, through the four fixing brackets of the flue
hood.
Connect the electrical cable from the control panel to
the fan unit, ensuring the plug connector is the cor-
rect way around and securely held.
(Illustration 15)
ILLUSTRATION 13b
Tighten the screws supplied for fixing the flue hood
by a few turns. Insert the seal between the flue hood
and the casing, exerting light pressure on it if
necessary. Tighten the screws with moderate force.