ATI SP 80, 120, 220, 300, 400 – INSTALLATION INSTRUCTIONS
Sept - 01
2 - INSTALLATION INSTRUCTIONS
2.1 REFERENCE REGULATIONS
The installation of this water heater must be carried out
in accordance with the relevant requirements of the
gas safety (installation and use) Regulations 1994, the
I.E.E. Wiring Regulations and the Bylaws of the Local
Water Authority, and the Building Regulations 1985.
Detailed recommendations are contained in the
following :
British Standard Code of Practice CP. 341 : 300-307 ;
CPP 342 : Parts 1 and 2 : BS 5440 Parts 1 & 2 : BS
5546 :BS 5854 : BS 6798 : BS 6891 : IGE/UP/2 Gas
Installation Pipework, Boosters and Compressors on
Industrial and Commercial Premises : BS 7206.
“The Gas Safety (Installation and Use) Regulations
1994 :
It is the law that all gas appliances are installed by
CORGI registered contractors in accordance with the
above regulations. Failure to install appliances
correctly could lead to prosecution. It is in your own
interest, and that of safety, to ensure that the law is
complied with”.
2.2 INSTALLATION RECOMMENDATIONS
•
The installation must be carried out by qualified
personnel, responsible for observing the current
safety standards and legislation and for the testing
•
The installation of this water heater must be carried
out strictly in accordance with the relevant
requirements of point 2.1.
•
During installation and maintenance, respect
carefully the instructions contained in this booklet.
Changes of any connections or the non-observance
of these instructions will cause the warranty to be
invalidated.
•
Before every operation of installation, maintenance
or repairing, remember to isolate the electrical
supply to the appliance.
•
For the flue connections use only original kit
supplied by the manufacturer of the appliance (they
have to be purchased separately according the kind
of installation that has to be carried out).
2.3 LOCATION OF THE APPLIANCE
As a type C gas appliance (room sealed), this water
heater can be installed in a room, without any
restrictions for air supply and for room volume. Where
the appliance is installed in a compartment the
following ventilation is required.
When the unit is installed as a single wall fan assisted
model (not room sealed), ventilation is required for
combustion and cooling air as listed below.
The flue pipe, in passing through the wall, must not be
cemented, in order to permit subsequent maintenance
of it. For this purpose the proper rosettes, issued in the
packaging of the appliance, can be used.
To prevent ingress of water during storms, it is
recommended that the air intake and flue pipe should
have a slight gradient downwards.
Models ATI SP 80 & 120
are for wall hung
installations. For this purpose the unit is to be mounted
using the two brackets at the back of the appliance,
towards the top (wall fixings not supplied).
Models ATI SP 220, 300 & 400
are for floor standing
installation. The water heater must stand on a level
non combustible base, suitable to support the weight
of the appliance, water content and any ancillary
equipment.
ATI SP 80, 120, 220, 300 & 400
Leave a space above the water heater of not less than
200 mm, in order to allow maintenance to the flue
hood and unit.
When locating the water heater there must be
consideration to the maximum permissible length of
the flue system chosen. Where the flue pipe passes
out through a side wall, guidance on siting the terminal
is given on page
Direct to Outside
To Internal Space
High and Low Level High and Low Level
ATI 80
23
45
ATI 120
23
45
ATI 220
131
261
ATI 300
140
279
ATI 400
140
279
MODEL
ALL FREE AREAS GIVEN IN CM²
MODEL
Direct to Outside
High Level Low Level High Level Low Level
ATI 80
23
45
45
90
ATI 120
23
45
45
90
ATI 220
131
261
261
522
ATI 300
140
279
279
558
ATI 400
140
279
279
558
To Internal Space
ALL FREE AREAS GIVEN IN CM²