AAP87600 PDU Specifications
System Specifications
A-9
lists the specifications for the AAP87600 PDU.
Table A-4. AAP87600 PDU: Specifications
Input Specifications
Power input
Single phase, AC
Nominal input voltage; frequency
200–240 VAC; 50/60 Hz
Current
†
† Denotes a maximum continuous input current of 16A at 240 VAC.
16 amps
Input receptacle
IEC 320/C20
Input protection
‡
‡ The circuit breaker is UL 489-listed and features a flat rocker front surface with an “Accidental Off”
feature. The circuit breaker has a delay curve similar to an AIRPAX
™
LEG series, delay 62.
16A, circuit breaker
Power dissipation
§
10W nom. @ 240 VAC
Panel indicators
¶
LED, main, and TVS
Output Specifications
Power output
††
3.84 KVA, maximum
Output receptacle
8x - IEC 320/C13
PE ground
‡‡
1/4” - 20 threaded stud
Physical and Environmental Specifications
Overall size
§§
Height: 1.72 in. (4.36 cm)
Width: 19.0 in. (48.26 cm)
Depth: 6.5 in. (16.51 cm)
Weight
5.7 lb (2.6 kg)
Operating temperature during
operation
32
F (0
C) to 131
F (55
C)
For every 800 ft (243.8m) above 2000 ft (609.6m), lower the
maximum operating temperature (95
F (35
C)) by 1.8
F
(1
C).
Maximum rate of temperature
change during operation
54
F (12
C) per hour or 32.36
F (0.2
C) per minute
Relative humidity during operation
10% to 80% (noncondensing)
Storage temperature to 40,000 ft
(12.2 km)
-38
F to 140
F (-40
C to 60
C)
Relative humidity during storage
5% to 95% (noncondensing)