Circuit Breaker
A Type-C circuit breaker with the following specification is required on the power line (subject to the
local electrical code).
Voltage
Circuit Breaker
100–120 VAC
15 A or 16 A
220-240 VAC
10 A
Table 3 Circuit breaker
Residual Current Device (RCD)
The wall outlet must be connected to a residual current device (RCD).
Power Connection
The customer must provide an appropriate power plug and have it installed by a certified electrician.
The following electrical outlets are required:
•
one outlet behind the printer
•
three outlets close to the printer (for the workstation, monitor, and servicing equipment)
UPS (Uninterrupted Power Supply)
It is recommended that the printer is powered through a UPS unit, provided by the customer. If
installed, the UPS ensures that—
•
the quality of printing is not affected by power fluctuations from the mains.
•
the printer can be programmed to perform “graceful shutdown” in the event of a power failure. This
is possible with some UPSs, such as the third-party Eaton PW9130G3000T.
The UPS specifications are listed below.
Eden260VS
Electrical Requirements
13