Para-
meter
Description of function
Setting range
Values
default
Alarm suppression after "Power-On" or
after a setpoint/alarm limits change
0...999 min.
0
Operating time before time depending load
replacement
0...999 (sec. or Min.)
240
Time scale for parameter A33
0: sec.
1: min.
1
Active measuring input
0: Sensor F1: temperature
1: Sensor F2: 4..20mA, pressure
0
Refrigerant
0: R134A
1: R22
2: R407C
3: R404A
4: R507
0
Activation of time-dependent
load replacement
0: not activated
1: activated
1
Sequential operation mode
0: not activated
1: activated
1
Operating mode
0: K1-K6 without load replacement
1: K1+K2 with load replacement
2: K1+K2 as bypass-group (K2)
3: K1-K3 with load replacement
4: K1-K4 with load replacement
5: K1-K4 as bypass-group (K2+K4)
with load replacement
6: K1-K5 with load replacement
7: K1-K6 with load replacement
8: K1-K6 as bypass-group (K2+K4+K6)
with load replacement
9: as 2, K2 inverted
10: as 5, K2+K4 inverted
11: as 8, K2+K4+K6 inverted
12: K1-K3 as bypass-group (K2)
13: K1-K6 as double bypass-group
(K2+K3,K5+K6) with load replacement
0
Switch mode relay K1
0: heating contact
1: cooling contact
1
Switch mode relay K2
0: heating contact
1: cooling contact
1
Switch mode relay K3
0: heating contact
1: cooling contact
1
Switch mode relay K4
0: heating contact
1: cooling contact
1
Switch mode relay K5
0: heating contact
1: cooling contact
1
Switch mode relay K6
0: heating contact
1: cooling contact
1
Setpoint offset
-20...+20.0 (bar or °C)
0.0
Password of parameter level
-99 ... 999
0