Order No.: 900310.050
Technical data of ST710-PWHVR.126
Input
E1:
External potential-free switching contact
Measuring input
F1:
Resistance thermometer Pt100-3L
Measuring range:
-200°C...350°C
Measuring accuracy: 0.5K +/- 0.5 % of scale range, without sensor
Operating range in case of temperature display like measuring range of the sensor, otherwise
-0.9...30.0 bar or –65...85 °C with R134A and -80...63 °C with R507.
F2:
linear current input, 4...20mA, 2-wire connection
Measuring accuracy: +/- 0.7 % of scale range, without sensor
The display range must be customised by parameter settings.
Operating range in case of pressure display like measuring range of the sensor, otherwise
–65...85 °C or -0.9...30.0 bar with R134A and -80...63 °C with R507.
Outputs
K1:
Relay, normally-open contact, 6A 250V
K2:
Relay, normally-open contact, 6A 250V
K3:
Relay, normally-open contact, 6A 250V
K4:
Relay, normally-open contact, 6A 250V
K5:
Relay, normally-open contact, 6A 250V
K6:
Relay, normally-open contact, 8A 250V
K7:
Relay, normally-open contact, 8A 250V
Please note:
The continuous current on terminal A, pin 9, is the accumulated current for relays K1
- K6 and may not exceed 8A!
Display
One 4-digit LED-display, height 12 mm, colour red
3 LEDs, diameter 3mm, for status displays
ST-Bus communication interface
Interface driver: RS485, galvanically not separated
The network has to be installed in lines topology and terminated with a 120 Ohm resistance on
each side.
In case of networking always connect port “A” with port “A” and port “B” with port “B”. Crossing over
is not permissible.
Power supply
12...24 V AC (50/60 Hz) or 16...36V DC, power consumption max 3 VA
Ambient conditions:
Storage temperature:
-20...+70°C
Operating temperature:
0...+55°C
Relative humidity:
max. 75% without dew
Gewicht
approx. 130 g