Plant
Para-
meter
Description of function
Setting range
Values
default
Function of relay K1 in case of sensor error 0: relay off
1: relay on
0
Function of relay K2 in case of sensor error 0: relay off
1: relay on
0
Function of relay K3 in case of sensor error 0: relay off
1: relay on
0
Function of relay K4 in case of sensor error 0: relay off
1: relay on
0
Function of relay K5 in case of sensor error 0: relay off
1: relay on
0
Function of relay K6 in case of sensor error 0: relay off
1: relay on
0
Selection setpoint 2 or Delta W1
0: Setpoint 2 (P1)
1: Delta W1 (P1r)
1
Selection setpoint 3 or Delta W2
0: Setpoint 3 (P2)
1: Delta W2 (P2r)
1
Selection setpoint 4 or Delta W3
0: Setpoint 4 (P3)
1: Delta W3 (P3r)
1
Selection setpoint 5 or Delta W4
0: Setpoint 5 (P4)
1: Delta W4 (P4r)
1
Selection setpoint 6 or Delta W5
0: Setpoint 6 (P5)
1: Delta W5 (P5r)
1
Temperature alarm mode
relative limits with
(
,
,
)
absolute limits with
(
,
,
)
0: Boundary alarm, relative limits
1: Boundary alarm, absolute limits
2: Range alarm, relative limits
3: Range alarm, absolute limits
4: as 0, but inverted
5: as 1, but inverted
6: as 2, but inverted
7: as 3, but inverted
0
Function of the buzzer and/or the display at
temperature alarm
0: no display, no buzzer
1: display flashes
2: only buzzer enabled
3: display flashes, buzzer enabled
4: as 2., alarm can be cancelled
5: as 3., buzzer can be cancelled
6: as 5., alarm returns after
1
New alarm after alarm acknowledging
0...360 min.
30
Minimum action time K1 "Off"
0...999 sec.
0
Minimum action time K2 "Off"
0...999 sec.
0
Minimum action time K3 "Off"
0...999 sec.
0
Minimum action time K4 "Off"
0...999 sec.
0
Minimum action time K5 "Off"
0...999 sec.
0
Minimum action time K6 "Off"
0...999 sec.
0
Mutual delay of contacts
0...999 sec.
0
Delay after “Power-on”
0...999 sec.
0