Temperature sensors
Para-
meter
Description of function
Setting range
Values
default
Mains frequency
0: 50Hz
1: 60Hz
0
Actual value of sensor F1
Measured value, not adjustable
Calibration sensor F1 (act. value correction)
-20...+20.0°C
0.0
Weighting factor sensor F1
0.50...1.50
1.00
Selection sensor F1
Depending on hardware, not all types are
available. Sensor will be deactivated in this
case.
0: not existent
1: PTC (-50…..+150°C)
2: Pt100 2-wire (-100…+600°C)
3: Pt100 3-wire (-100…+500°C)
4: NTC
(-40……+40°C)
5: Pt1000 2-wire (-100…+330°C)
6: Pt1000 3-wire (-100…+300°C)
7: 0-20mA
8: 4-20mA
9: 0-10V
2
Software filter sensor F1
1 ... 32
12
Display at 0/4mA and sensor
=7/8/9
-99..+999
0.0
Display at 20mA and sensor
=7/8/9
-99..+999
100
Actual value of sensor F2
Measured value, not adjustable
Calibration sensor F2 (act. value correction)
-20...+20.0°C
0.0
Weighting factor sensor F2
0.50...1.50
1.00
Selection sensor F2
see
8
Software filter sensor F2
1 ... 32
16
Display at 0/4mA and sensor
=7/8/9
-99..+999
2.0
Display at 20mA and sensor
=7/8/9
-99..+999
30.0
Password of parameter level
-99 ... 999
0
Pre-defined parameter sets
(password-protected)
Para-
meter
Description of function
Setting range
Values
default
Parameter set
0: Temperature sensor
1: Pressure sensor, refrigerant R134A
2: Pressure sensor, refrigerant R22
3: Pressure sensor, refrigerant R407C
4: Pressure sensor, refrigerant R404A
5: Pressure sensor, refrigerant R507
0
Password for entering level selection
(
in display)
-99 ... 999
-19
Password of parameter level
-99 ... 999
-19
Warning: Changes made in the parameter set will change
all
parameter settings!
Parameter
can only be viewed and set via ST-bus.
Summary of Contents for ST710-PWHVR.126