Sensor selection F1 / F2
With this parameter, you can define the sensor
type. Depending on the hardware, not all sensor
types may be supported. For the NTC sensor, a
parallel resistor will have to be connected.
,
Software filter F1 / F2
In this parameter, you can define how many meas-
ured values are to be used for calculating a mean
value. A mean value is calculated from the last
measured values, with the oldest measured value
being deleted (so called "Moving Average Filter").
,
F1/F2: Display at 0mA / 4mA / 0V
If, when choosing the sensor
/
= 7, 8 or 9
is selected (0/4…20mA or 0...10V linear sensor),
you can define via this parameter which value is to
be displayed in the case of a current of 0 or 4mA or
a voltage of 0V. The value to be displayed for
20mA/10V can be defined in the next parameter.
The actual measured value is calculated as linear
interpolation between these two values.
,
F1/F2: Display at 20mA / 10V
If, when choosing the sensor
/
= 7, 8 or 9
is selected (0/4…20mA or 0...10V linear sensor),
you can define via this parameter which value is to
be displayed in the case of a current of 20mA or a
voltage of 10V. The display value for 0/4mA or 0V
is defined in the previous parameter. The actual
measured value is calculated as linear interpolation
between these two values.
Password for parameter level
This parameter sets the password for level
.
Pre-defined parameter
sets
(password-protected)
Intern: active data set
With this parameter, you can set up pre-defined
data sets. The data sets are provided by Störk-
Tronic. If a new data set is loaded, all previously set
parameters will be overwritten. After that, they can
be edited as required. The most important settings
are shown in the appendix. Basically the different
refrigerants are configured.
Password for accessing level selection
With this parameter, you can set the level selection
password, i.e. in display
. In the standard design,
access to level selection is blocked by password
.
Password of parameter level
With this parameter, you can set the password for
parameter level
.