INSTRUCTION MANUAL
GB
–
4/5
4) Position the VIGIBELT
®
TOUCH detectors on the openings and screw the M6 brake nuts with the washers
(clamping torque 4 N.m) according to
Figure-D.
5) Connect the VIGIBELT
®
TOUCH according to the electrical scheme E or F:
NC detector = positive safety, permanent control of the proper functioning of the sensor
Signal loss indicates that there is a
strap offset problem
Electrical wire cut off
3-wire/NC connection scheme E
colours
BN = Brown
BU = Blue
BK = Black
PVC cable 3x0.11mm² 2m for ATEX zone and non-
ATEX
3-wire connection scheme F
Colours
1 = Black
2 = Grey
4 = Blue
PVC cable 2m for non ATEX 3x0.25mm²
figure D
Attach the VIGIBELT
®
Touch with
washers and lock nuts
For low voltage sensor, ATEX or not
-
3-wire cable connection
-
L=2m cable
-
Voltage 12-24V DC
-
Voltage limits, including ripple, 10-36V DC
-
Switching power
≤
100 mA
-
temperature Operating: -25... 70°C (Non-ATEX)
-20... 60°C (ATEX)
-
Protection - IP67
Caution: Any connection must be made outside the
ATEX zone
For mechanical sensor, out of ATEX zone
-
3-wire cable connection
-
L=2m cable
-
Tension 12… 250V AC/DC
-
NC : Black wire (1) / Grey wire (2)
-
NO : Black wire (1) / Blue wire (4)
-
Operating temperature: -20... 105°C
-
Protection - IP67
Caution: Any connection must be made outside the
ATEX zone