System layout 10
Arr 10
VBus
10
9
The controller calculates the temperature difference between
collector sensor S1 and tank sensor S2. If the difference is
larger than or identical to the adjusted switch-on temperature
difference (DT O), the solar pump will be operated by relay 1,
and the tank will be loaded until the switch-off temperature
difference (DT F) or the maximum tank temperature (S MX)
is reached.
If the maximum collector temperature (CMX) is reached, the
solar pump will be operated by relay 1 and the 3-way-valve will
S1
S2
S4 / TR
R1
S3
R2
Display Channels
Channel
Description
Terminal
Page
COL
x
Temperature collector
S1
37
TST
x
Temperature tank
S2
37
S3
x
Temperature sensor 3
S3
37
S4
x
Temperature sensor 4
S4
37
TR
x*
Temperature return sensor
S4
37
n %
x
Pump speed relay
R1
30
h P1
x
Operating hours R1
R1
38
h P2
x
Operating hours R2
R2
38
kWh
x*
Heat quantity kWh
-
38
MWh
x*
Heat quantity MWh
-
38
TIME
x
Time
-
34
be operated by relay 2 in order to direct the surplus energy to a
heat dump. For security purpose this will be carried out only if
the tank temperature is below the non-adjustable emergency
shutdown of 200 °F.
Sensors S3 and S4 can optionally be connected for
measurement purposes.
If energy metering (OHQM) is activated, sensor S4 has to be
connected as return sensor.