12
R2
S1
S2
R1
S3
S4 / TR
System layout 3
The controller calculates the temperature difference between
collector sensor S1 and tank sensor S2. If the difference is
larger than or identical to the adjusted switch-on temperature
difference (DT O), the solar pump will be operated by relay 1,
and the tank will be loaded until the switch-off temperature
difference (DT F) or the maximum tank temperature (S MX)
is reached.
Sensor S3 is used for a thermostatic function, which operates
Arr 3
Display Channels
Channel
Description
Terminal
Page
INIT
x*
ODB initialization active
-
37
FLL
x*
ODB filling time active
-
37
STAB
x*
ODB stabilization in progress
-
37
COL
x
Temperature collector
S1
37
TSTB
x
Temperature tank 1 bottom
S2
37
TSTT
x
Temperature tank 1 at the top
S3
37
TDIS
s*
Thermal disinfection temperature
S3
37
S4
x
Temperature sensor 4
S4
37
TR
x*
Temperature return sensor
S4
37
n1 %
x
Pump speed R1
R1
38
h P1
x
Operating hours R1
R1
38
h P2
x
Operating hours R2
R2
38
kWh
x*
Heat quantity kWh
-
38
MWh
x*
Heat quantity MWh
-
38
CDIS
s*
Countdown of monitoring period
-
38
SDIS
s*
Starting time display
-
38
DDIS
s*
Heating period display
-
38
TIME
x
Time
-
34
relay 2 for backup heating or heat dump purposes, when
the adjusted thermostat switch-on temperature (AH O) is
reached. This function can optionally be combined with up
to three adjustable time frames.
Sensor S3 can also be optionally used as a reference sensor
for the thermal disinfection function OTD.
Sensor S4 can optionally be connected for measurement
purposes. If energy metering (OHQM) is activated, sensor S4
has to be connected as return sensor.