The controller calculates the temperature differences between
collector sensor S1 and tank sensors S2 and S3. If the
differences are larger than or identical to the adjusted switch-
on temperature differences (DT1O / DT2O), the solar pump will
be operated by relay 1, and the respective tank zone will be
loaded until the switch-off temperature differences (DT1F /
DT2F) or the maximum tank temperatures (S1MX / S2MX) are
S4 / TR
Arr 4
Display Channels
Channel
Description
Terminal
Page
COL
x
Temperature collector
S1
37
TSTB
x
Temperature tank 1 bottom
S2
37
TSTT
x
Temperature tank 1 at the top
S3
37
S4
x
Temperature sensor 4
S4
37
TR
x*
Temperature return sensor
S4
37
n %
x
Pump speed relay
R1
38
hP1
x
Operating hours R1
R1
38
hP2
x
Operating hours R2
R2
38
kWh
x*
Heat quantity kWh
-
38
MWh
x*
Heat quantity MWh
-
38
TIME
x
Time
-
34
reached. The priority logic causes priority loading of the upper
zone of the tank, if possible. The 3-way-valve will be operated
by relay 2 then.
Sensor S4 can optionally be connected for measurement
purposes.
If energy metering (OHQM) is activated, sensor S4 has to be
connected as return sensor.