background image

ŝÄ

’ZH<ŝŗTVB.eB

qqqĪZ`.<é<`VHCĪHB

.CZ`<<`.HC

.CZ`<<`.HC

9. Installation

Only qualified contractors should carry out installation, commis-
sioning, maintenance and repair.

Observe the accident prevention instructions.

 

Note

For hydraulic reasons, never connect more than five col-
lectors in series. Where several rows of collectors are 
fitted, they must be connected in parallel.

 

Note

The type-test approbation is invalidated if more than 30 
collectors are grouped together to form a single hydraulic 
assembly. An individual inspection is required for larger 
systems.

 

Note

Commercial systems, the open content of which exceeds 
10 litres and is not more than 50 litres, require notifica-
tion to the relevant local authority [in Germany - check 
local regulations].

 

Damage to the appliance and environment

When filling the solar thermal system, for frost and corro-
sion protection use only the heat transfer medium men-
tioned in the chapter "Specification/Data table".

9.1 Preparations

Provide all pipe runs to the building interior on site.

9.2 Pipework 

installation

Use copper, stainless steel or corrugated stainless steel hoses 
when installing the flow and return lines. With a system com-
prising up to four collectors, we recommend a pipe diameter of 
Ø 18 x 1.0.

Avoid sawing off pipes to prevent swarf entering the system. Use 
a pipe cutter for swarf-free cutting. 

Earth the pipework in accordance with current regulations.

9.2.1 Soldered 

lines

Soldered lines must be brazed. Use solder to DIN EN 1044: CP105 
and CP203. Use this solder without flux. Only solder gunmetal 
and brass fittings with flux F-SH-1 to EN 1045. Other flux has a 
detrimental effect on corrosion resistance.

9.2.2 Alternative 

lines

Seal lines made with locking ring fittings, press fittings and cor-
rugated hoses by suitable means. Seals must be resistant to glycol 
and temperatures up to 180 °C. 

 

Damage to the appliance and environment

The thermal insulation may only be applied following a 
successful tightness test.

9.3 

Air vent valve

Install a lockable manual air vent valve at high points of the system 
or route a ventilation line to a manual air vent valve. Automatic 
quick-acting air vent valves installed close to the collector must 
be separated from the system with a shut-off valve.

9.4 Safety 

valve

 

Damage to the appliance and environment

There must not be any shut-off appliances between the 
collectors and the safety valve.

The safety valve drain must discharge into a container that can 
hold the entire content of the system. In the case of smaller sys-
tems, the empty heat transfer medium can is adequate.

9.5 Drain 

facility

 

f

Install a drain valve at the lowest point of the solar thermal 
system.

Summary of Contents for SOL 23 Premium

Page 1: ...CeC eC CZ HC HT V HC C CZ HC e Z HC CZ HC eZH CZ x HC H Z eC Z H HV C THq V e T H HV HV VHH C V HC T eV ZH V T e T V HVB C THeV C V HC C H eV H HV T CH Ze H TV Z x HC ZH TV B eB...

Page 2: ..._________________30 10 2 Lifting onto the roof____________________________________________ 31 10 3 Installation of collectors next to each other ______________ 31 10 4 Installing the collectors above...

Page 3: ...ach other The collector is designed for a rafter roof with a tensioned underlay and for a tiled roof The at plate collector converts light into heat The light penetrates the glass cover This is made f...

Page 4: ...onsult a qualified contractor The pump appears to start late and switch itself off early Please consult a qualified contractor The pump starts and switches itself off again shortly afterwards This rep...

Page 5: ...ment Do not leave the collector unsecured If the collector falls over the glass may shatter 8 Appliance description This collector is speci cally designed for on end roof integration The laser welded...

Page 6: ...x 1 0 Avoid sawing off pipes to prevent swarf entering the system Use a pipe cutter for swarf free cutting Earth the pipework in accordance with current regulations 9 2 1 Soldered lines Soldered line...

Page 7: ...g 1b Manual air vent valve 2 Control unit 2a Outside temperature sensor 2k Temperature sensor in the collector sensor well 2s Solar thermal system cylinder temperature sensor 3f Solar thermal system D...

Page 8: ...uare area with a side length A 8 Roof outlets D E 26_05_01_0607 0 5 m b 2 m 1 m b 2 m b 2 but 1 m D 2 m Roof outlets include components that protrude more than 0 35 m above the upper edge of the roof...

Page 9: ...2 1 Rope 2 Collector 26_05_01_0442 10 3 Installation of collectors next to each other installation height up to 20 m on tiled roof 10 3 1 Overview Both illustrations below provide an preliminary over...

Page 10: ...the second and third batten at to secure the lead ashing above the batten that is on edge Damage to the appliance and the environment Ensure that a hollow channel in which rainwater may be come trappe...

Page 11: ...ft hand collector on the left hand mark ing for the outlet The ow line can be tted on the right or left with the return line being tted accordingly on the opposite side Note Ensure that there are no r...

Page 12: ...d side ashing is secured on to the left hand collector accordingly 10 3 5 Roof outlet f Remove the cover of the collector connection 26_05_01_0626 f Insert the plug in connection of the roof outlet wi...

Page 13: ...ning protection for the collectors is to be installed by a con tractor before the roo ng work is carried out see chapter Light ning protection 10 3 8 Sealing 1 1 1 26_05_01_0278 1 Sealing strips f Fit...

Page 14: ...s for the upper row of collectors spaced 400 mm apart similar to the lower row of collectors two battens at the bottom and one at the top at a distance of 2080 mm from the inside edge of the mounting...

Page 15: ...tor casing mounting frame and pipework into the exist ing lightning protection system 10 6 1 Collector casing lightning protection 26_05_01_0299 1 1 Lightning protection Connect the collector to the l...

Page 16: ...connect the collector array to the ushed pipework f Using at gaskets and union nuts attach the corrugated pipes to the collector connections and the collector sensor well The corrugated stainless stee...

Page 17: ...t The thermal insulation may only be applied following a successful tightness test f Re ll the system f Using the ll pump generate a pressure of 0 5 MPa 5 bar f The test pressure must not drop for a p...

Page 18: ...which is integrated into the system f Check whether all required relays of the solar control unit are connected f Set the control unit back to automatic mode The system should then start automatically...

Page 19: ...nserted into the sensor well The pump is running but no flow rate is discernible at the flow meter with balancing valve The flow and return temperatures are identical or the cylinder temperature does...

Page 20: ...ng There are two pos sible causes if this occurs later The system pressure is too low The pump draws in air via the air vent valve Check whether the selected expansion vessel is large enough Check the...

Page 21: ...perature C 218 Min operating pressure MPa 0 35 Max permissible pressure MPa 0 6 Pressure drop at 300 l h MPa 0 0035 Test pressure MPa 1 7 Test medium Water at the factory Heat transfer medium H 30 L L...

Page 22: ...on fi www stiebel eltron fi France STIEBEL ELTRON SAS 7 9 rue des Selliers B P 85107 57073 Metz C dex 3 Tel 0387 7438 88 Fax 0387 7468 26 info stiebel eltron fr www stiebel eltron fr Hungary STIEBEL E...

Reviews: