The pump starts and switches itself off again 

shortly afterwards. This repeats a few times 

until the system runs correctly. The same hap-

pens in the evening.

 

 

 

 

There is still too little insolation to heat up the en-

tire pipework.

Check for faults again when there is strong insolation.

The flow rate is too high (the pump is set too high). Reduce the output stage of the pump.

The switching temperature differential of the con-

troller is set too low.

Increase the switching temperature differential on the con-

troller.

The pipework is not fully insulated.

Insulate all pipes.

The cylinder and collector sensors are inter-

changed. (The problem occurs after commission-

ing).

Connect the temperature sensors to the correct sensor termi-

nals (see the control unit installation and operating instruc-

tions).

The pressure gauge indicates a drop in pres-

sure.

 

 

 

 

 

 

 

 

 

 

A pressure drop shortly after the system is filled 

is quite normal, as air is still escaping from the 

system. A pressure drop later on can be caused by 

an air lock that has shifted. In addition, during nor-

mal operation the pressure fluctuates by 0.02-0.03 

MPa depending on the system temperature. If the 

pressure drops continuously, the system is leaking 

somewhere. 

Is the automatic air vent valve closed?

Check the fittings, the glands on shut-off gate valves and the 

threaded connections. Check the soldered joints.

Check the pre-charge pressure of the expansion vessel and 

ensure the diaphragm is not leaking.

 

 

 

Fluid loss as a result of opening the safety valve, 

because the expansion vessel is not large enough, 

or it is unpressurised or faulty. Collector damage 

(leaking) and frost damage through insufficient 

antifreeze content.

Check the vessel size. Check the antifreeze content and the 

pH value.

 

 

The pump runs noisily.

Air in the pump

Vent the pump.

Inadequate system pressure

Increase the system pressure. 

The system runs noisily. This is normal in the 

first few days after filling. There are two pos-

sible causes if this occurs later:

 

The system pressure is too low. The pump draws in 

air via the air vent valve.

Check whether the selected expansion vessel is large enough. 

Check the pre-charge pressure of the expansion vessel. In-

crease the system pressure.

The pump rate is set too high.

Switch to a lower speed and check the flow rate at the flow 

meter (with balancing valve).

The cylinder cools down over night. After the 

pump has switched off, the flow and return 

operate at different temperatures. At night the 

collector temperature is higher than the out-

side temperature.

 

 

 

The gravity brake does not close.

 

 

 

Check the position of the adjusting screw. Check the gravity 

brake for leaks. Has a swarf become jammed or are there dirt 

particles on the sealing surface? 

Single pipe circulation for short pipework with low 

pressure drop.

 

 

Change the line routing. Never connect the solar heat 

exchanger directly but draw the supply lines first in a U 

downwards. The siphon assists the gravity brake. If required, 

install a two-way valve that is switched simultaneously with 

the pump.

Reheating does not work. The boiler runs 

briefly, stops and starts again. This repeats 

frequently, until the cylinder has reached its 

set temperature.

There is air in the reheat heat exchanger.

Vent the reheat heat exchanger. 

The heat exchanger surface area is too small.

 

 

Compare the details supplied by the boiler manufacturer with 

those supplied by the cylinder manufacturer. The problem 

may be resolved by selecting a higher flow temperature at 

the boiler.

The cylinder cools down excessively.

 

 

The insulation is faulty or incorrectly fitted.

Check whether the insulation is intact. Insulate the cylinder 

connections.

Incorrect setting of the control unit for reheating.

Check the setting on the boiler control unit.

DHW circulation runs too frequently and/or at night. Check the switching times and the interval operation.

The pump does not switch off.

 

Sensor faulty or incorrectly positioned.

Check the sensor position, installation and curves.

The control unit is faulty

Note: The variable speed pump does not switch off immedi-

ately but only after it reaches its lowest speed.

Summary of Contents for SOL 23 Premium

Page 1: ...CeC eC CZ HC HT V HC C CZ HC e Z HC CZ HC eZH CZ x HC H Z eC Z H HV C THq V e T H HV HV VHH C V HC T eV ZH V T e T V HVB C THeV C V HC C H eV H HV T CH Ze H TV Z x HC ZH TV B eB...

Page 2: ..._________________30 10 2 Lifting onto the roof____________________________________________ 31 10 3 Installation of collectors next to each other ______________ 31 10 4 Installing the collectors above...

Page 3: ...ach other The collector is designed for a rafter roof with a tensioned underlay and for a tiled roof The at plate collector converts light into heat The light penetrates the glass cover This is made f...

Page 4: ...onsult a qualified contractor The pump appears to start late and switch itself off early Please consult a qualified contractor The pump starts and switches itself off again shortly afterwards This rep...

Page 5: ...ment Do not leave the collector unsecured If the collector falls over the glass may shatter 8 Appliance description This collector is speci cally designed for on end roof integration The laser welded...

Page 6: ...x 1 0 Avoid sawing off pipes to prevent swarf entering the system Use a pipe cutter for swarf free cutting Earth the pipework in accordance with current regulations 9 2 1 Soldered lines Soldered line...

Page 7: ...g 1b Manual air vent valve 2 Control unit 2a Outside temperature sensor 2k Temperature sensor in the collector sensor well 2s Solar thermal system cylinder temperature sensor 3f Solar thermal system D...

Page 8: ...uare area with a side length A 8 Roof outlets D E 26_05_01_0607 0 5 m b 2 m 1 m b 2 m b 2 but 1 m D 2 m Roof outlets include components that protrude more than 0 35 m above the upper edge of the roof...

Page 9: ...2 1 Rope 2 Collector 26_05_01_0442 10 3 Installation of collectors next to each other installation height up to 20 m on tiled roof 10 3 1 Overview Both illustrations below provide an preliminary over...

Page 10: ...the second and third batten at to secure the lead ashing above the batten that is on edge Damage to the appliance and the environment Ensure that a hollow channel in which rainwater may be come trappe...

Page 11: ...ft hand collector on the left hand mark ing for the outlet The ow line can be tted on the right or left with the return line being tted accordingly on the opposite side Note Ensure that there are no r...

Page 12: ...d side ashing is secured on to the left hand collector accordingly 10 3 5 Roof outlet f Remove the cover of the collector connection 26_05_01_0626 f Insert the plug in connection of the roof outlet wi...

Page 13: ...ning protection for the collectors is to be installed by a con tractor before the roo ng work is carried out see chapter Light ning protection 10 3 8 Sealing 1 1 1 26_05_01_0278 1 Sealing strips f Fit...

Page 14: ...s for the upper row of collectors spaced 400 mm apart similar to the lower row of collectors two battens at the bottom and one at the top at a distance of 2080 mm from the inside edge of the mounting...

Page 15: ...tor casing mounting frame and pipework into the exist ing lightning protection system 10 6 1 Collector casing lightning protection 26_05_01_0299 1 1 Lightning protection Connect the collector to the l...

Page 16: ...connect the collector array to the ushed pipework f Using at gaskets and union nuts attach the corrugated pipes to the collector connections and the collector sensor well The corrugated stainless stee...

Page 17: ...t The thermal insulation may only be applied following a successful tightness test f Re ll the system f Using the ll pump generate a pressure of 0 5 MPa 5 bar f The test pressure must not drop for a p...

Page 18: ...which is integrated into the system f Check whether all required relays of the solar control unit are connected f Set the control unit back to automatic mode The system should then start automatically...

Page 19: ...nserted into the sensor well The pump is running but no flow rate is discernible at the flow meter with balancing valve The flow and return temperatures are identical or the cylinder temperature does...

Page 20: ...ng There are two pos sible causes if this occurs later The system pressure is too low The pump draws in air via the air vent valve Check whether the selected expansion vessel is large enough Check the...

Page 21: ...perature C 218 Min operating pressure MPa 0 35 Max permissible pressure MPa 0 6 Pressure drop at 300 l h MPa 0 0035 Test pressure MPa 1 7 Test medium Water at the factory Heat transfer medium H 30 L L...

Page 22: ...on fi www stiebel eltron fi France STIEBEL ELTRON SAS 7 9 rue des Selliers B P 85107 57073 Metz C dex 3 Tel 0387 7438 88 Fax 0387 7468 26 info stiebel eltron fr www stiebel eltron fr Hungary STIEBEL E...

Reviews: