background image

HTV`.HC

`VHe<Z+HH`.C&

ŝō

’ZH<ŝŗTVB.eB

qqqĪZ`.<é<`VHCĪHB

6. Troubleshooting

The following contains descriptions of what measures to take in 
order to remedy problems. If you are still unable to fix the problem 
using this information, please consult your heating contractor.

%|şùŒ

|şń¼

f

V¼ă¼®ź

Fault/error message at the controller

There is a fault in the system; the sensor is faulty or incor-

rectly connected.

Please refer to the controller operating and installation 

instructions.

Pressure fluctuations in the system

If the problem occurs immediately after commissioning, 

there is air in the solar circuit.

Please consult a qualified contractor.

The collectors are misted up.

 

Moisture has got in during storage.

 

The internal mist will evaporate after a few weeks 

in operation. The moisture will progressively escape 

through the integral ventilation slots.

The pump does not run although the collector 

is hotter than the cylinder (no noise from the 

motor, no noticeable vibrations).

 

The maximum cylinder or collector temperature is ex-

ceeded. The control indicator or display on the controller 

is activated.

The controller has shut down correctly and restarts 

again automatically when the actual temperature 

drops below the selected maximum temperature.

The power supply is interrupted.

Check fuses/MCBs.

Other cause

Please consult a qualified contractor.

The pump is running, but no flow rate is 

discernible at the flow meter with balancing 

valve. The flow and return temperatures are 

identical or the cylinder temperature does not 

rise or rises only slowly.

 

 

 

 

Please consult a qualified contractor.

 

 

 

The pump is running, but no flow rate is 

discernible at the flow meter with balancing 

valve.

The shut-off valve is closed.

Open the shut-off valve.

Other cause

Please consult a qualified contractor.

The pump appears to start late and switch 

itself off early.

 

 

Please consult a qualified contractor.

The pump starts and switches itself off again 

shortly afterwards. This repeats a few times 

until the system runs correctly. The same hap-

pens in the evening.

There is still too little insolation to heat up the entire 

pipework.

Check for faults again when there is strong insolation.

Other cause

Please consult a qualified contractor.

The pressure gauge indicates a drop in pres-

sure.

 

 

 

 

A pressure drop shortly after the system is filled is quite 

normal, as air is still escaping from the system. A pres-

sure drop later on can be caused by an air lock that has 

shifted. In addition, during normal operation the pressure 

fluctuates by 0.02-0.03 MPa depending on the system 

temperature. If the pressure drops continuously, the sys-

tem is leaking somewhere. 

Please consult a qualified contractor.

 

  

 

 

 

The pump runs noisily.

 

Please consult a qualified contractor.

The system runs noisily. This is normal in the 

first few days after filling. If this occurs later:

 

Please consult a qualified contractor.

The cylinder cools down over night. After the 

pump has switched off, the flow and return 

operate at different temperatures. At night the 

collector temperature is higher than the out-

side temperature.

The gravity brake does not close.

 

 

Check the position of the adjusting screw on the grav-

ity brake.

Other cause

Please consult a qualified contractor.

Reheating does not work. The boiler runs 

briefly, stops and starts again. This repeats 

frequently, until the cylinder has reached its 

set temperature.

  

 

 

Please consult a qualified contractor. 

 

 

The cylinder cools down excessively.

 

Please consult a qualified contractor.

The pump does not switch off.

 

The control unit is faulty.

The variable speed pump does not switch off immedi-

ately but only after it reaches its lowest speed.

Other cause

Please consult a qualified contractor.

Summary of Contents for SOL 23 Premium

Page 1: ...CeC eC CZ HC HT V HC C CZ HC e Z HC CZ HC eZH CZ x HC H Z eC Z H HV C THq V e T H HV HV VHH C V HC T eV ZH V T e T V HVB C THeV C V HC C H eV H HV T CH Ze H TV Z x HC ZH TV B eB...

Page 2: ..._________________30 10 2 Lifting onto the roof____________________________________________ 31 10 3 Installation of collectors next to each other ______________ 31 10 4 Installing the collectors above...

Page 3: ...ach other The collector is designed for a rafter roof with a tensioned underlay and for a tiled roof The at plate collector converts light into heat The light penetrates the glass cover This is made f...

Page 4: ...onsult a qualified contractor The pump appears to start late and switch itself off early Please consult a qualified contractor The pump starts and switches itself off again shortly afterwards This rep...

Page 5: ...ment Do not leave the collector unsecured If the collector falls over the glass may shatter 8 Appliance description This collector is speci cally designed for on end roof integration The laser welded...

Page 6: ...x 1 0 Avoid sawing off pipes to prevent swarf entering the system Use a pipe cutter for swarf free cutting Earth the pipework in accordance with current regulations 9 2 1 Soldered lines Soldered line...

Page 7: ...g 1b Manual air vent valve 2 Control unit 2a Outside temperature sensor 2k Temperature sensor in the collector sensor well 2s Solar thermal system cylinder temperature sensor 3f Solar thermal system D...

Page 8: ...uare area with a side length A 8 Roof outlets D E 26_05_01_0607 0 5 m b 2 m 1 m b 2 m b 2 but 1 m D 2 m Roof outlets include components that protrude more than 0 35 m above the upper edge of the roof...

Page 9: ...2 1 Rope 2 Collector 26_05_01_0442 10 3 Installation of collectors next to each other installation height up to 20 m on tiled roof 10 3 1 Overview Both illustrations below provide an preliminary over...

Page 10: ...the second and third batten at to secure the lead ashing above the batten that is on edge Damage to the appliance and the environment Ensure that a hollow channel in which rainwater may be come trappe...

Page 11: ...ft hand collector on the left hand mark ing for the outlet The ow line can be tted on the right or left with the return line being tted accordingly on the opposite side Note Ensure that there are no r...

Page 12: ...d side ashing is secured on to the left hand collector accordingly 10 3 5 Roof outlet f Remove the cover of the collector connection 26_05_01_0626 f Insert the plug in connection of the roof outlet wi...

Page 13: ...ning protection for the collectors is to be installed by a con tractor before the roo ng work is carried out see chapter Light ning protection 10 3 8 Sealing 1 1 1 26_05_01_0278 1 Sealing strips f Fit...

Page 14: ...s for the upper row of collectors spaced 400 mm apart similar to the lower row of collectors two battens at the bottom and one at the top at a distance of 2080 mm from the inside edge of the mounting...

Page 15: ...tor casing mounting frame and pipework into the exist ing lightning protection system 10 6 1 Collector casing lightning protection 26_05_01_0299 1 1 Lightning protection Connect the collector to the l...

Page 16: ...connect the collector array to the ushed pipework f Using at gaskets and union nuts attach the corrugated pipes to the collector connections and the collector sensor well The corrugated stainless stee...

Page 17: ...t The thermal insulation may only be applied following a successful tightness test f Re ll the system f Using the ll pump generate a pressure of 0 5 MPa 5 bar f The test pressure must not drop for a p...

Page 18: ...which is integrated into the system f Check whether all required relays of the solar control unit are connected f Set the control unit back to automatic mode The system should then start automatically...

Page 19: ...nserted into the sensor well The pump is running but no flow rate is discernible at the flow meter with balancing valve The flow and return temperatures are identical or the cylinder temperature does...

Page 20: ...ng There are two pos sible causes if this occurs later The system pressure is too low The pump draws in air via the air vent valve Check whether the selected expansion vessel is large enough Check the...

Page 21: ...perature C 218 Min operating pressure MPa 0 35 Max permissible pressure MPa 0 6 Pressure drop at 300 l h MPa 0 0035 Test pressure MPa 1 7 Test medium Water at the factory Heat transfer medium H 30 L L...

Page 22: ...on fi www stiebel eltron fi France STIEBEL ELTRON SAS 7 9 rue des Selliers B P 85107 57073 Metz C dex 3 Tel 0387 7438 88 Fax 0387 7468 26 info stiebel eltron fr www stiebel eltron fr Hungary STIEBEL E...

Reviews: