MAINTENANCE 

 
 

The SB series tank is an extremely simple device and as such requires 

very little maintenance.  There are, however, several items that should be 

checked out on an annual or as needed basis to ensure a reliable supply 
of hot water: 
 

1)

 

On an annual basis, remove the jacket cover over the hand hole 
and make sure that the hand hole gasket is leak-tight.  On the 40 
and 50-gallon sizes, this hand hole is located on the top of the SB 
tank and is accessed by removing the two screws holding the cover 

to the top of the SB tank. 

2)

 

Make sure that the rest of the boiler and domestic water piping is 
free of leaks. 

3)

 

If there is an oil-lubricated circulator in the system, make sure that it 
is lubricated as called for by the circulator manufacturer. 

4)

 

The SB tank depends upon the boiler for source of heat and is 
therefore only as reliable as the boiler.  Make sure that the boiler is 
maintained in accordance with the boiler manufacturer’s 

instructions. 

5)

 

All SB tanks are equipped with a sacrificial anode rod.  This anode 
rod helps to protect the SB tank from corrosion.  This anode rod 
should be inspected periodically and replaced if more than half of 
the anode has been corroded away at any point in its length.  The 
rate at which the anode rod will deteriorate will depend upon the 
quantity and chemistry of the water passing through the tank.  In 

general, an annual inspection of the anode rod is appropriate. 

6)

 

On an annual basis, check the operation of the Temperature and 
Pressure Relief Valve by lifting the lever on the top of the valve and 
confirming that water is released. 

 

 
 
 
 
 

IMPORTANT

 

 
For the anode rod to work properly it must be electrically bonded to the 
SB Tank.  On the SB150 and SB200, this is done with two ground wires that 
bond the anode rod to the clean-out cover and the clean-out cover to 
the tank. 

 

Whenever the anode rod or clean out cover is serviced on the 

SB150 or SB200, be sure that these ground wires are reconnected. 

 
Failure to follow these precautions could result in premature failure of the 
tank. 

Summary of Contents for SB 150

Page 1: ...Phone 413 247 3380 800 582 8423 Fax 413 247 3369 E mail info stiebel eltron usa com SB 150 SB 200 Glass Lined Indirectly Fired Water Heaters With Single Heat Exchanger INSTALLATION AND OPERATING INST...

Page 2: ...nk opens periodically it may be due to thermal expansion in a closed water supply system Consult a licensed plumber the local plumbing authority or the water supplier Do not plug the Temperature and P...

Page 3: ...o not install valves reducing couplings or other obstructions in the relief valve discharge line Do not install a T P valve with a pressure settings in excess of 150 PSI or a temperature setting in ex...

Page 4: ...50 SB 200 First hour rating gal hr 192 225 Boiler water output btu hr 103 149 116 094 Boiler water flow gal min 8 0 8 0 Coil head loss ft w c 2 6 2 6 Coil surface sq ft m2 12 1 1 12 14 3 1 32 Tank vol...

Page 5: ...5 Dimensions in cm Model SB 150 SB 200 A 5 1 8 13 02 5 1 8 13 02 B 9 3 4 24 76 9 3 4 24 76 C 34 86 36 37 7 8 96 20 D E 50 1 2 128 27 62 3 4 159 38 F 20 1 2 20 1 2...

Page 6: ...6...

Page 7: ...7...

Page 8: ...with the boiler manufacturer s instructions 5 All SB tanks are equipped with a sacrificial anode rod This anode rod helps to protect the SB tank from corrosion This anode rod should be inspected perio...

Page 9: ...hat may arise in connection with a warranty claim or any incidental or consequential expenses This warranty does not apply to conditions resulting from a failed component or part that is not part of t...

Reviews: