50
| acW Basic
WWW.stieBel-eltron.com
installation
specification
17.3 specification
acW 25i basic
acW 35i basic
acW 50i basic
acW 25mi basic
acW 35mi basic
230348
230349
230350
230357
230358
Can be combined with
CuR 25i basic
CuR 35i basic
CuR 50i basic
CuR 2-54i basic
CuR 2-54i basic
Operating mode
Cooling/heating/
dehumidifying/
recirculating air mode
Cooling/heating/
dehumidifying/
recirculating air mode
Cooling/heating/
dehumidifying/
recirculating air mode
Cooling/heating/
dehumidifying/
recirculating air mode
Cooling/heating/
dehumidifying/
recirculating air mode
Power consumption
W
38
42
52
38
42
Power connection
1/N/PE 230-240 V
~50 Hz
1/N/PE 230-240 V
~50 Hz
1/N/PE 230-240 V
~50 Hz
1/N/PE ~ 230 V 50Hz
1/N/PE ~ 230 V 50Hz
Power consumption
A
0,16
0,2
0,24
0,16
0,2
IP-Rating
IP20
IP20
IP20
IP20
IP20
Refrigerant
R410 A
R410 A
R410 A
R410 A
R410 A
Colour
white
white
white
white
white
Height
mm
250
265
292
250
265
Width
mm
710
790
920
710
790
Depth
mm
195
195
225
195
195
Weight
kg
8
9
11,5
8
9
Air volume, low
m³/h
350
420
600
350
420
Air volume, medium
m³/h
480
520
750
480
520
Air volume, high
m³/h
570
620
800
570
620
Sound pressure level low at a
distance of 1 m
dB(A)
28
29
37
28
29
Sound pressure level medium at a
distance of 1 m
dB(A)
33
35
40
33
35
Sound pressure level high at a
distance of 1 m
dB(A)
39
40
44
39
40
Operating range cooling min./
max.
°C
20/32
20/32
20/32
20/32
20/32
Operating range, heating min./
max.
°C
20/27
20/27
20/27
20/27
20/27
Internal/external electrical
connecting cables *
mm²
4 x 1,5
4 x 1,5
4 x 2,5
4 x 1,0
4 x 1,0
Power supply cable *
mm²
3 x 1,5
3 x 1,5
3 x 2,5
3 x 2,5
3 x 2,5
Fuses
A
C16
C16
C25
C25
C25
Pipe diameter, liquid line
mm
6x1
6x1
6x1
6x1
6x1
Pipe diameter, suction gas line
mm
10x1
12x1
12x1
10x1
12x1
Condensate drain
mm
16
16
16
16
16
* acc. to type of routing C (VDE 0100 part 430, VDE 0298-4)
Further specifications can be found in the external unit installation instruc-
tions.
Cooling and heating output are substantially subject to the external unit used,
as well as the appliance configuration for multi-split appliances. Correspond-
ing output details are given on the rating plate and in the external unit instal-
lation instructions.
Rated details to EN 14511, sound pressure level of internal appliance measured
at 1 m distance.
!
Risk of damage
Never operate the appliance outside the specified
temperature application limits. If the appliance is
operated outside the specified temperature application
limits, this can cause internal protection mechanisms
to respond. If operation is prolonged, there is a risk of
damage.
.